Technical data
14.4 AC voltage supply
Note
The power supply contains an active PFC (Power Factor Correction) circuit to conform to the
EMC guidelines.
Uninterruptible AC power systems (UPS) must supply a sinusoidal output voltage in the
normal and buffered mode when used with SIMATIC PCs with an active PFC.
UPS characteristics are described and classified in the standards EN 50091-3 and IEC
62040-3. Devices with sinusoidal output voltage in the normal and buffered mode are
identified with the classification "VFI-SS-...." or "VI-SS-....".
Power supply characteristics
Input data
Voltage
Continuous current
Starting current (load-independent)
Active power
Apparent power
Output data
Voltages
Secondary power output
Power Good signal of the AC power supply
182
AC power supply
Nominal 100 - 240 V AC
(-15% / +10%),
widerange
Max. 2.3 A
to 50 A for 1 ms
190 W
250 VA
+5 V / 16.5 A * (18.5 A peak)
+3.3 V / 8.5 A *
* total of 90 W permitted
+12 V / 6.5 A (8 A peak)
-12 V / 0.3 A
Max. 150 W