Specifications; Control Power; Waste Electrical And Electronic Equipment (Weee); Excitation Power - Allen-Bradley 1407-CGCM-DLR User Manual

Combination generator control module
Table of Contents

Advertisement

Source
Phases
(1)
Single-phase
PMG
PMG
3-phase
(2)
Single-phase
SE
SE
3-phase
SE
3-phase
SE
3-phase
SE
3-phase
(1) PMG = Permanent Magnet Generator.
(2) SE = Separately Excited.

Specifications

The CGCM-DLR unit electrical and physical characteristics are listed in the
following tables.

Control Power

Supply
18...32V DC (24V DC nom)
(A 24V Nominal Battery or 24V DC Power Supply
with ATEX certification powers the unit.)
AC ripple, max

Waste Electrical and Electronic Equipment (WEEE)

At the end of its life, this equipment should be collected separately from any
unsorted municipal waste.

Excitation Power

Wiring Configuration
PMG-A and PMG-C
Floating Wye
PMG-A and PMG-C
Floating Wye
Grounded Wye
(grounded neutral)
Floating delta
Open delta, floating
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Burden
30 W
50%, 50...120 Hz
Voltage
Min 56 Vrms
Max 300 Vrms
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 56 Vrms
Max 300 Vrms
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 56 Vrms L-L
Max 300 Vrms L-L
Appendix
Frequency
VA (Max)
Min 50 Hz
3070
Max 342 Hz
Min 50 Hz
3070
Max 342 Hz
Min 50 Hz
3070
Max 342 Hz
Min 50 Hz
3070
Max 342 Hz
Min 50 Hz
3070
Max 342 Hz
Min 50 Hz
3070
Max 342 Hz
Min 50 Hz
3070
Max 342 Hz
D
209

Advertisement

Table of Contents
loading

Table of Contents