Remote Excitation Enable Input; Open Collector Outputs (Fault Relay And Redundancy Relay); Field Output - Allen-Bradley 1407-CGCM-DLR User Manual

Combination generator control module
Table of Contents

Advertisement

Appendix D
Specifications
212

Remote Excitation Enable Input

Attribute
Voltage rating
Input impedance
Logical high voltage, min
Logical low voltage, max

Open Collector Outputs (fault relay and redundancy relay)

Attribute
Voltage rating
Voltage range
Rated current, max

Field Output

Attribute
Continuous voltage
Continuous current
10-second forcing voltage
10 second forcing current
Field resistance, min
(1) Available output voltage is dependent on magnitude of excitation power input voltage.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Value
24V DC nom
5.6K Ω
18V DC
5V DC
Value
24V DC nom
18...30V DC
500 mA
Value
32, 63, 125V DC
15 A DC
50, 100, or 200V DC
30 A DC
2.13 Ω
32V DC
4.2 Ω
63V DC
8.3 Ω
125V DC
(1)