Related Parameters
• GenVT_Config
• BusVT_Config
• GenRated_V
Load Share Page
The Load Share page is used to configure the unit parameters that are related to
the real power load-sharing function of the unit.
• Full Scale Voltage - Sets the load share output voltage when the generator is
producing rated real power. The tag LS_FS_V in the configuration table
stores this value, expressed in volts.
• Limit - Sets the maximum per unit load share error reported to the host
controller. The tag LSLimit in the configuration table stores this value,
expressed in per unit power.
• Rate - Sets the maximum change in the load share error per CGCM-DLR
unit update cycle. The tag LSRate in the configuration table stores this
value, expressed in seconds per rated watts.
Related Parameters
• GenRated_W
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019