Differences Between Embedded Hsc And Plug-In Module; Counter Specifications - Allen-Bradley Micro800 2080-MEMBAK-RTC2 User Manual

Plug-in modules
Table of Contents

Advertisement

Chapter 4
High Speed Counter – 2080-MOT-HSC
Differences Between
Embedded HSC and Plug-in
Module

Counter Specifications

26
The following table lists the differences between the embedded HSC and the
2080-MOT-HSC plug-in module.
Embedded HSC
Limited to 100 kHz
12/24V input
None
Dedicated preset and hold inputs
None
When using the 2080-MOT-HSC module, the high and low preset
IMPORTANT
status does not automatically reset. When using the embedded HSC,
it automatically resets when the high and low preset condition no
longer exists.
Filter and decode inputs: 3 input points A, B, Z
These input points may come from different types and configurations of sensors.
The user must configure the module to respond to the type of sensor connected
to the module as described below. This can be configured in the 2080-MOT-
HSC UDFB. From Connected Components Workbench Release 8.0 onwards, if
you have configured the plug-in for Feedback Axis, you can also edit the input
filter values in the plug-in configuration module properties.
Nominal Filter Settings
No Filter – Default
250 kHz (DC 2 µs)
200 kHz (DC 2.5 µs)
80 kHz (DC 6.25 µs)
40 kHz (DC 12.5 µs)
13.3 kHz (DC 37.6 µs)
10 kHz (DC 50 µs)
4 kHz (DC 125 µs)
2 kHz (DC 250 µs)
1 kHz (DC 0.5 ms)
500 Hz (DC 1 ms)
250 Hz (DC 2 ms)
125 Hz (DC 4 ms)
62.5 Hz (DC 8 ms)
31.25 Hz (DC 16 ms)
50% duty
2080-MOT-HSC Plug-in Module
Up to 250 kHz
12/24V input or 5V differential line driver
Embedded rate calculation using "Per Pulse" and
"Cyclic" methods
Configure either preset or hold inputs
One 5/24V output
Maximum Guaranteed
Block Pulse Width
617 kHz (DC 0.81 µs)
352 kHz (DC 1.42 µs)
135 kHz (DC 3.7 µs)
62.5 kHz (DC 8.0 µs)
20.8 kHz (DC 24.1 µs)
15.7 kHz (DC 31.8 µs)
6.3 kHz (DC 79.3 µs)
3.2 kHz (DC 156 µs)
1.6 kHz (DC 0.31 ms)
778 Hz (DC 0.642 ms)
389 Hz (DC 1.285 ms)
195 Hz (DC 2.6 ms)
97.3 Hz (DC 5.14 ms)
48.5 Hz (DC 10.3 ms)
Rockwell Automation Publication 2080-UM004D-EN-E - March 2018
Minimum Guaranteed Pass
Pulse Width
263kHz (DC 1.9 µs)
201 kHz (DC 2.48 µs)
86.2 kHz (DC 5.8 µs)
42.5 kHz (DC 11.76 µs)
14.1 kHz (DC 35.5 µs)
10.5 kHz (DC 47.2 µs)
4.2 kHz (DC 119 µs)
2.1 kHz (DC 237 µs)
1.0 kHz (DC 0.5 ms)
526 Hz (DC 0.95 ms)
263 Hz (DC 1.9 ms)
131 Hz (DC 3.81 ms)
65.8 Hz (DC 7.6 ms)
32.9 Hz (DC 15.2 ms)