Allen-Bradley 1407-CGCM-DLR User Manual page 128

Combination generator control module
Table of Contents

Advertisement

Chapter 5
CGCM-DLR Unit Startup
128
Phase Rotation Error (47)
Follow these steps to test that the Phase Rotation Error function is working
properly.
1. Apply simulated generator voltage signals by using the test voltage source,
opposite to the configured phase rotation.
2. Adjust the simulated generator voltage to the rated generator voltage.
3. Verify that a phase rotation fault alarm is annunciated following the
expected delay.
Generator Over-current (51)
Follow these steps to test that the Generator Over-current function is working
properly.
1. Apply simulated generator voltage and current signals by using the test
current and voltage source.
2. Adjust the simulated generator voltage to rated generator voltage.
3. Adjust the current above the desired test trip time point on the selected
over-current curve.
4. Verify that a generator over-current alarm is annunciated following the
expected delay.
The delay is a function of the curve, time dial selections, voltage restraint
settings, and the simulated generator current and voltage applied.
5. Repeat as desired to verify various points on the characteristic curve
selected.
Reconnect All Permanent Connections
After all static testing, connect all permanent connections that were temporarily
removed. These connections can include VT and CT input connections,
excitation power, and exciter field connections.
See the system installation and wiring documentation.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019

Advertisement

Table of Contents
loading

Table of Contents