Chapter 6
CGCM-DLR Unit Software Interface
Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4
Byte
Size in
Type
Bits
Bytes
0
1
SINT
N/A
1
3
SINT
N/A
4
1
BOOL
0
BOOL
1
BOOL
2
BOOL
3
BOOL
4
BOOL
5
BOOL
6
BOOL
7
158
The Set Attributes Single service for instance 4 of the Assembly Object can access
the following information.
Table 17 - Set Attributes Single (Service Code 0x10)
Name
Attribute ID
Data
3
Use of this service is not recommended. Writing the CGCM-DLR unit
IMPORTANT
configuration with unscheduled messaging is not recommended. We
recommend that you use only scheduled configuration messaging that is sent
when the connection is opened or the module configuration is edited in the
Logix Designer application.
Configuration Checking
When configuration data is received, the CGCM-DLR unit verifies that
individual parameters are within the minimum and maximum values that are
indicated in
Table 18
parameter is detected, the CGCM-DLR unit enters a configuration fault mode
and ignores all data in the configuration write. The Connection tab in the
module configuration dialog box in the Logix Designer application displays an
error code that corresponds to the first offending configuration parameter. The
CGCM-DLR unit does not perform any application checks (for example, is a
value suitable for the particular application) or dependency checks (for example,
is a value reasonable based on other values entered).
Data Table
Tag Name
Space Reserved for Logix controller Revision Configuration Number
Pad Bytes Reserved for Logix controller Usage
RevVARFltOutEn
RevPwrFltOutEn
OvrExcFltOutEn
Ovr_I_FltOutEn
Undr_V_FltOutEn
OvrVFltOutEn
UndrFreqFltOutEn
OvrFreqFltOutEn
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Data Type
UINT
(for example, perform range checking). If an out-of-range
Description
Units
Reverse VAR Fault Output Enable
-
Reverse Power Fault Output
Enable
Over-excitation Fault Output
Enable
Over-current Fault Output Enable
Undervoltage Fault Output
Enable
Overvoltage Fault Output Enable
Under-frequency Fault Output
Enable
Over-frequency Fault Output
Enable
Value
See Unscheduled Configuration Read/
Write Data Table, Assembly Instance 4
Range
Error Code
0=Disabled,
1=Enabled