Output (scheduled write) Data Table

The Output data table contains time-critical command and setpoint data that is
written to the CGCM-DLR unit by the ControlLogix controller.
The host controller automatically writes the data in this Controller Tag to the
unit at the scheduled update rate whenever a connection between the two exists.
This write occurs independently of the user program. The Output data table can
also be read and written by using unscheduled messaging. An unscheduled write
message is not accepted if there is a scheduled connection active.
Data Type
The Output data table is automatically created by using module-defined data
type AB:1407_CGCM:O:1.
Assembly Object Instance 1 - Output Data Table (scheduled write)
The Get Attributes Single service for instance 1 of the Assembly Object can
access the following information.
Table 8 - Get Attributes Single (Service Code 0x0E)
Name
Attribute ID
Data
3
Size
4
The Set Attributes Single service for instance 1 of the Assembly Object
(Class 0x04) can access the following information.
Table 9 - Set Attributes Single (Service Code 0x10)
Name
Attribute ID
Data
3
Set Attribute Single is supported for this instance only when there is no
TIP
scheduled connection to it. Otherwise it returns a device state conflict error
0x0010.
Configuration Checking
No range checks are performed on the Output data table.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
CGCM-DLR Unit Software Interface
Data Type
UINT
UINT
Data Type
UINT
Chapter 6
Value
See Output (scheduled write) Data
Table, Assembly Instance 1
56
Value
See Output (scheduled write)
Data Table, Assembly Instance 1
149