Redundancy Outputs from CGCM-DLR Unit

• CGCM_Flt - This tag indicates, if the CGCM-DLR unit is still capable,
that the CGCM-DLR unit has a detected an internal failure.
• CGCMInControl - This tag indicates that the CGCM-DLR unit has
hardware and software excitation enabled.
• Spare1 - When operating in Redundant mode, this tag indicates the
CGCM-DLR unit has assumed the role of primary and is providing
excitation to the generator.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Detailed CGCM-DLR Unit Tag Descriptions
Appendix E
245