Chapter 4
CGCM-DLR Unit Configuration
112
Voltage Page
The Voltage page is used to configure the unit parameters that are related to the
voltage protection and compensation functions.
Overvoltage
• Setpoint - Establishes the overvoltage setpoint. This setpoint is stored in
tag Ovr_V_Setpt in the configuration table and scaled in per cent rated
generator volts.
• Delay - Establishes the time the generator voltage must be above the
overvoltage setpoint before the CGCM-DLR unit annunciates an
overvoltage fault. This setpoint is stored in tag Ovr_V_TimeDly in the
configuration table and scaled in seconds.