Appendix A
Time Over-current Characteristic Curves
Table 35 - 51P and 51N Time Characteristic Curve Constants
Curve
Curve Name
Selection
1
S, Short Inverse
2
S2, Short Inverse
3
L1, Long Inverse
4
L2, Long Inverse
5
D, Definite Time
6
M, Moderately Inverse
7
I, Inverse Time
8
Inverse Time
9
V, Very Inverse
10
V2, Very Inverse
11
Extremely Inverse
12
E2, Extremely Inverse
13
Standard Inverse
14
B, Very Inverse (I
15
Extremely Inverse (I
16
Long Time Inverse (I
17
Fixed Time
Time Over-current
Characteristic Curve
Graphs
178
Trip Characteristic Constants
A
0.2663
0.0286
5.6143
2.3955
0.4797
0.3022
8.9341
0.2747
5.4678
4.4309
7.7624
4.9883
0.01414
2
1.4636
t)
2
8.2506
t)
2
12.1212
t)
0.0000
The following illustrations show the characteristic curves of the CGCM-DLR.
Equivalent time dial settings were calculated at a value of five times pickup.
The
Characteristic Curve Cross-reference
existing electromechanical relay characteristics.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
B
C
N
0.03393
1.000
1.2969
0.02080
1.000
0.9844
2.18592
1.000
1.000
0.00000
1.000
0.3125
0.21359
1.000
1.5625
0.12840
1.000
0.5000
0.17966
1.000
2.0938
0.10426
1.000
0.4375
0.10814
1.000
2.0469
0.09910
1.000
1.9531
0.02758
1.000
2.0938
0.01290
1.000
2.0469
0.00000
1.000
0.0200
0.00000
1.000
1.0469
0.00000
1.000
2.0469
0.00000
1.000
1.0000
1.00000
1.000
0.0000
table cross-references each curve to
Reset
K
R
0.028
0.5000
0.028
0.0940
0.028
15.750
0.028
7.8001
0.028
0.8750
0.028
1.7500
0.028
9.0000
0.028
0.8868
0.028
5.5000
0.028
5.8231
0.028
7.7500
0.028
4.7742
0.028
2.0000
0.028
3.2500
0.028
8.0000
0.028
29.0000
0.028
1.0000

Advertisement