Allen-Bradley 1407-CGCM-DLR User Manual page 153

Combination generator control module
Table of Contents

Advertisement

Table 12 - Unscheduled Read Data Table, Assembly Instance 5
Byte
Size in
Type
Bytes
0
4
Real
4
4
Real
8
4
Real
12
4
Real
16
4
Real
20
4
Real
24
4
Real
28
4
Real
32
4
Real
36
4
Real
40
4
Real
44
4
Real
48
4
Real
52
4
Real
56
4
Real
60
4
Real
64
4
Real
68
4
Real
72
4
Real
For instance, a 30 MVA machine operating at 10% load yields an energy tag limit
of:
(8,338,600 * 0.1 * 30000) = 25,015,800,000 kVAh, or 2.50158 x 10
When the energy tag value exceeds 8,338,600, rounding of the value begins to
occur.
The energy values are not retentive. When the CGCM-DLR unit powers up or
re-establishes a connection with the controller, the energy presets in the
Unscheduled Write table are written to the energy metering values.
Data Table
Tag Name
Description
AvgPF
Average Power Factor
PhA_PF
Phase A Power Factor
PhB_PF
Phase B Power Factor
PhC_PF
Phase C Power Factor
Total_kVA
Total kVA
PhA_kVA
Phase A kVA
PhB_kVA
Phase B kVA
PhC_kVA
Phase C kVA
PhA_kW
Phase A kW
Ph_B_kW
Phase B kW
PhC_kW
Phase C kW
Total_kVAR
Total kVAR
PhA_kVAR
Phase A kVAR
PhB_kVAR
Phase B kVAR
PhC_kVAR
Phase C kVAR
Avg_I
Average Current
PhA_I
Phase A Current
PhB_I
Phase B Current
PhC_I
Phase C Current
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
CGCM-DLR Unit Software Interface
10
Units
Range
PF
-1...1
kVA
0...3E+09
kW
-3E+09...3E+09
kVAR
A
0...60,000
Chapter 6
kVAh
153