• Under-frequency Delay - Establishes the amount of time in seconds that
the frequency must be below the under-frequency setpoint before the unit
annunciates the fault. This parameter is stored in tag UndrFreqTimeDly
in the configuration table.
Related Parameters
• EngineIdle
• SoftStartTime
Power Page
The Power page is used to configure parameters that are related to reverse power
and reverse reactive power protection. A higher setpoint value corresponds to
larger reverse power or VAR flow before a fault is declared.
• Reverse kW setpoint - Establishes the generator reverse kW setpoint in
percent of rated VA. The tag Rev_kW_Setpt stores this value in the
configuration table.
• Reverse kW Fault Delay - Establishes the amount of time in seconds that
the reverse kW must be above the reverse kW setpoint before the
CGCM-DLR annunciates the fault. This parameter is stored in tag
Rev_kW_TimeDly in the configuration table.
• Reverse kVAR setpoint - Establishes the generator reverse kVAR setpoint
in percent of rated VA. The tag Rev_kVAR_Setpt stores this value in the
configuration table.