Chapter 4
CGCM-DLR Unit Configuration
90
Generator Page
The Generator page is used to configure the unit to the design ratings of the
generator. Enter the generator nameplate ratings in the appropriate fields of the
Generator page.
Rated Frequency - Sets the generator rated frequency in Hz. Sets the value of tag
GenRatedFreq in the Configuration table.
Rated Voltage - Sets the generator rated line-to-line voltage in volts AC. Sets the
value of tag GenRated_V in the Configuration table.
Rated Current - Sets the generator's rated current in amperes AC. Sets the value
of tag GenRated_I in the Configuration table.
Rated Power - Sets the generator rated power in watts. Sets the value of tag
GenRated_W in the Configuration table.
Rated Field Voltage - Sets the generator exciter rated field voltage while the
generator is operating at rated voltage, kW, and kVAR. Sets the value of tag
GenRatedExcV in the Configuration table.
Rated Field Current - Sets the generator exciter rated field current, in amperes
DC. This current is the current that must be supplied to the exciter while the
generator is operating at rated voltage, kW, and kVAR. Sets the value of tag
GenRatedExcI in the Configuration table.