Allen-Bradley 1407-CGCM-DLR User Manual page 91

Combination generator control module
Table of Contents

Advertisement

Transformers Page
The Transformers page is used to match the unit with the configuration of the
generator voltage and current sensing transformers. To configure the Transformer
page, you must know the system wiring configuration. The settings that are
entered on the Transformers page must correspond to the actual wiring
configuration.
See
Chapter
2, Installation, for information on various wiring configurations.
See the VT and CT manufacturer data for assistance to enter the correct primary
and secondary voltages.
• Generator VT Configuration - The generator VT configuration selections
are (1) single-phase, (2) two-transformer open delta, (3) three-wire Wye,
and (4) four-wire Wye. Use the two-transformer open delta setting for any
delta configuration. This parameter is stored in the tag GenVT_Config in
the configuration table.
• Generator VT Primary Voltage - The primary voltage rating of the
generator voltage transformer is stored in tag GenVT_Pri_V in the
configuration table.
• Generator VT Secondary Voltage - The secondary voltage rating of the
generator voltage transformer that is connected to V Gen A, V Gen B, and
V Gen C (and V Gen N for Wye configurations) of the CGCM-DLR unit.
This parameter is stored in tag GenVT_Sec_V in the configuration table.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
CGCM-DLR Unit Configuration
Chapter 4
91