Appendix D
Specifications
214
Over-excitation Voltage Protection
Attribute
Pickup
Time delay
Over-current Protection
Attribute
Pickup
Time delay
Undervoltage Protection
Attribute
Pickup
Time delay
Overvoltage Protection
Attribute
Pickup
Time delay
Loss of Sensing Protection
Attribute
Pickup
Time delay
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Range
1...200V DC
0.1...30 s
Range
Increment
10...320% of rated
1%
generator current
Characteristic inverse
0.1 s
per ANSI C50.13
configurable
Range
Increment
60...100% of rated
1%
generator voltage
0.1...300 s
Range
Increment
100...140% of rated
1%
generator voltage
0.1...300 s
Value
See text description in Operation section of the manual for this item
0.1 s for normal operation, 1 s during soft start
Increment
1V DC
0.1 s
Accuracy
±2% rated current
Accuracy
±2% rated voltage
±0.1 s
Accuracy
±2% rated voltage
±0.1 s