Over-Excitation Voltage Protection; Over-Current Protection; Undervoltage Protection; Overvoltage Protection - Allen-Bradley 1407-CGCM-DLR User Manual

Combination generator control module
Table of Contents

Advertisement

Appendix D
Specifications
214

Over-excitation Voltage Protection

Attribute
Pickup
Time delay

Over-current Protection

Attribute
Pickup
Time delay

Undervoltage Protection

Attribute
Pickup
Time delay

Overvoltage Protection

Attribute
Pickup
Time delay

Loss of Sensing Protection

Attribute
Pickup
Time delay
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Range
1...200V DC
0.1...30 s
Range
Increment
10...320% of rated
1%
generator current
Characteristic inverse
0.1 s
per ANSI C50.13
configurable
Range
Increment
60...100% of rated
1%
generator voltage
0.1...300 s
Range
Increment
100...140% of rated
1%
generator voltage
0.1...300 s
Value
See text description in Operation section of the manual for this item
0.1 s for normal operation, 1 s during soft start
Increment
1V DC
0.1 s
Accuracy
±2% rated current
Accuracy
±2% rated voltage
±0.1 s
Accuracy
±2% rated voltage
±0.1 s

Advertisement