Allen-Bradley 1407-CGCM-DLR User Manual

Combination generator control module
Table of Contents

Advertisement

Quick Links

User Manual
Original Instructions
Combination Generator Control Module
Catalog Numbers 1407-CGCM-DLR

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley 1407-CGCM-DLR

  • Page 1 User Manual Original Instructions Combination Generator Control Module Catalog Numbers 1407-CGCM-DLR...
  • Page 2 Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
  • Page 3: Table Of Contents

    Table of Contents Preface Summary of Changes ......... . . 9 Additional Resources .
  • Page 4 Create a New Module in the ControlLogix Controller ... 76 Create the New 1407-CGCM-DLR Module in the I/O Configuration..........76 Electronic Keying.
  • Page 5 Table of Contents Chapter 6 CGCM-DLR Unit Software Introduction ..........139 CGCM-DLR Unit Data Table Summary.
  • Page 6 Table of Contents Assembly Object (class code 0x04) ......208 Appendix D Specifications ............. 209 Control Power .
  • Page 7 Table of Contents Inputs to CGCM Unit........222 Outputs from CGCM-DLR Unit.
  • Page 8 Table of Contents Reverse Power Protection Inputs to CGCM-DLR Unit ..234 Reverse Power Protection Outputs from CGCM Unit ..235 Rotating Diode Monitor Inputs to CGCM-DLR Unit ..235 Rotating Diode Monitor Outputs from CGCM Unit .
  • Page 9: Preface

    Preface The information in this manual applies to the 1407-CGCM-DLR module, Series D, Revision A or later, with host firmware revision 05.25 or later, and EtherNet/IP® DLR firmware revision 01.09 or later. The manual notes differences with earlier versions of the product where they occur.
  • Page 10: Studio 5000 Environment

    Preface Studio 5000 Environment The Studio 5000® Engineering and Design Environment™ combines engineering and design elements into a common environment. The first element in the Studio 5000® environment is the Logix Designer application. The Logix Designer application is the rebranding of RSLogix™ 5000 software and continues to be the product to program Logix5000 controllers for discrete, process, batch, motion, safety, and drive-based solutions.
  • Page 11: General Information

    Chapter General Information Introduction The Combination Generator Control Module with EtherNet/IP® Device Level Ring communication (CGCM-DLR unit) is a microprocessor-based control and protection device. The CGCM-DLR unit is designed to integrate with a Logix family programmable controller to provide generator control, protection, and synchronization functions.
  • Page 12: Generator Protection Functions

    Chapter 1 General Information Generator Protection Functions This list contains the generator protection functions: • Loss of excitation current (40) • Over-excitation voltage (59F) • Generator overvoltage (59) • Generator undervoltage (27) • Loss of sensing (60FL) • Loss of permanent magnet generator (PMG/Excitation power) (27) •...
  • Page 13: Inputs

    • Pulse-width modulated output power stage that is rated at 15 A • Discrete redundancy relay output • Discrete fault output driver • Load sharing connection for use with the Allen-Bradley® Line Synchronization Module™ (1402-LSM) or compatible hardware Communication Interfaces The CGCM-DLR unit has these three communication ports: •...
  • Page 14 Chapter 1 General Information Notes: Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 15: Installation

    Chapter Installation Mounting Requirements This equipment is intended for use in a Pollution Degree 2 Industrial Environment, in overvoltage Category II applications (as defined by IEC publication 60664-1). Because the units contain a heat sink, they must be mounted vertically. Any other mounting angle reduces the heat dissipation capabilities of the units, which can lead to premature failure of critical components.
  • Page 16 Chapter 2 Installation Figure 1 - CGCM-DLR Unit Overall Dimensions 247.7 (9.75) 228.6 (9.00) (0.38) 152.4 (6.00) 355.6 (14.00) (~14.3) IP ADDRESS 192.168.1.1XY 00-87, 89-98 RESTORE FACTORY DEFAULTS SELECTED PER DHCP OR USER ENTERED 152.4 (6.00) 1/4 - 20 Ground Stud (2 Places) 25.4 (1.00)
  • Page 17: Electrical Connections

    Installation Chapter 2 Electrical Connections The CGCM-DLR unit connections are dependent on the application and excitation scheme. All inputs or outputs cannot be used in a given installation. Incorrect wiring can result in damage to the unit. Connect the CGCM-DLR unit terminals with copper wire rated for a minimum of 600V.
  • Page 18 Chapter 2 Installation Table 1 - Terminal Block Label Description Terminal Block Wire Gauge Label Description Range ID(+)1 A 1 A cross-current compensation CT input 2.6…2.1 mm (10…12 AWG) ID(+)5 A 5 A cross-current compensation CT input ID(-) Cross-current compensation CT common input I3(+)1 A 1 A phase C CT input I3(+)5 A...
  • Page 19: Excitation Power

    Installation Chapter 2 Excitation Power Excitation power is wired to the PMG terminals, whether connected to the generator output (Shunt Excited) or to a PMG. Connect shunt excited inputs with a voltage transformer (VT). PMG inputs are on TB1 and are labeled PMG A, PMG B, and PMG C, to illustrate their respective phase relationships.
  • Page 20 Chapter 2 Installation Figure 5 - Excitation Power Connections, 3-phase Shunt Fuse PMG A PMG B Fuse PMG C SHLD 1 SHLD 1 Figure 6 - Excitation Power Connections, AREP Generator This diagram is based on a Leroy Somer 300 kW AREP (auxiliary-winding regulation excitation principle) machine.
  • Page 21: Excitation Output

    Installation Chapter 2 Excitation Output The excitation outputs are on TB2 and are labeled EXC(+) and EXC(-). Twisted, shielded cabling is required for the excitation outputs. Figure 7 - Excitation Output Connections, Non-redundant CGCM Exciter voltage connections Shld2 Shld2 EXC (-) EXC (+) Exciter field When the redundancy function is used, three or four external flyback diodes in...
  • Page 22: Chassis Ground

    Chapter 2 Installation Chassis Ground The terminal that is labeled CH GND, on TB4, is the chassis ground. Ground studs are also provided on the lower part of the mounting flanges and are internally connected to the CH GND terminal. Connect chassis ground to earth ground with minimum 2.6 mm (10 AWG) copper wire that is attached to either stud on the lower part of either side of the unit.
  • Page 23 For assistance in wiring a CGCM-DLR unit in a power system configuration that is not shown in this manual, contact your local Allen-Bradley Distributor or Rockwell Automation sales representative. Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 24 Chapter 2 Installation Figure 9 - Voltage and Current Connection for Two (or Three) Transformer Delta Bus and Two (or Three) Transformer Delta Generator System L1 L2 L3 Fuse Optional Ground Fuse VBus A VBus B VBus C Use of a third potential Fuse VBus N transformer is optional.
  • Page 25 Installation Chapter 2 Figure 10 - Voltage and Current Connection for Four-wire Wye Bus and Four-wire Wye Generator System with Grounded Neutral L2 L3 Fuse Fuse VBus A VBus B VBus C Fuse VBus N TB 6 Fuse Fuse VGen A VGen B VGen C Fuse...
  • Page 26 Chapter 2 Installation Figure 11 - Voltage and Current Connection for Four-wire Wye Bus and Two (or Three) Transformer Delta Generator System L2 L3 Fus e Fuse VB u s A VB u s B VB u s C Fu se VB u s N TB 6 Fuse...
  • Page 27 Installation Chapter 2 Figure 12 - Voltage and Current Connection for Two (or Three) Transformer Delta Bus and Four-wire Wye Generator System L2 L3 Fu se Optional Ground VB us A Fu se VBus B VB us C VB us N TB 6 Fuse Use of a third potential...
  • Page 28 Chapter 2 Installation Figure 13 - Voltage and Current Connection for Three-wire Wye Bus and Four-wire Wye Generator System with Grounded Neutral L 1 L2 L3 Fuse Fuse VBus A VBus B VBus C Fuse VBus N TB 6 Fuse Fuse VGen A VGen B...
  • Page 29 Installation Chapter 2 Figure 14 - Voltage and Current Connection for Dual Breaker Bus and Two (or Three) Transformer Delta Generator System L1 A L 2A L 3 A L1 B L 2B L 3 B Fu s e VB us A VB us B Fu se VB us C...
  • Page 30 Chapter 2 Installation Figure 15 - Voltage and Current Connection for Dual Breaker Bus and Four-wire Wye Generator System L1 A L 2A L3 A L1B L2 B L3B Fuse VBus A VBus B Fuse VBus C VBus N TB 6 Fuse Fuse V Gen A...
  • Page 31 Installation Chapter 2 Figure 16 - Voltage and Current Connection for Single-phase Bus and Single-phase Generator System L2 L3 Fuse VBus A VBus B VBus C VBus N TB 6 VGen A Fuse VGen B VGen C VGen N TB 5 To optional cross-current reactive compensation loop.
  • Page 32: Auxiliary Input

    Chapter 2 Installation Figure 17 - Current Connections for 3-phase Delta Generator with Two CTs The connections that are shown in this diagram can be used if only two CTs are available in the generator circuit. Two CTs can be used only with a three-wire delta generator.
  • Page 33 Installation Chapter 2 Fault Relay Output The fault relay output is an open-collector sinking output. The fault relay output terminals are on TB4 and are labeled FLT. The following illustration shows a typical connection. Figure 18 - Typical Fault Relay Connection Redundancy Relay Output The redundancy relay output is an open-collector sinking output.
  • Page 34 Chapter 2 Installation Figure 20 - Typical Redundancy Current-sensing Connection Diagram Generator I1 ( -) Current I1 (+) 5 A I1 (+) 1 A Typical connection for Connections CGCM 1 TB 3 one current input. Other current inputs (including the cross-current input) should duplicate.
  • Page 35: Real-Power Load Sharing

    Installation Chapter 2 Real-power Load Sharing The load sharing terminals connect to a 0…5V DC, internally powered circuit. The load sharing terminals are on TB7 and are labeled LS(+) and LS(-). Terminal SHLD4 is provided to land the cable shield. Twisted, shielded cabling is required for the load sharing connections.
  • Page 36 Chapter 2 Installation Figure 24 - Cross-current (Reactive Differential) Compensation Connection Diagram L 1 L2 Cross- ID (+ ) 1A current CT ID (+ ) 5A (typical) ID (-) TB 3 Customer Supplied CT Shorting Switch or Test Block (typical) ID (+ ) 1 A ID (+ ) 5 A ID ( -)
  • Page 37: Communication Connectors And Settings

    Installation Chapter 2 Communication Connectors and Settings There are three ports on the unit: the factory calibration port, the redundancy port (COM1), and the EtherNet/IP® network port. Factory Calibration Port The factory calibration port is not intended for use by anyone other than qualified factory representatives.
  • Page 38 Chapter 2 Installation EtherNet/IP Network Port Two EtherNet/IP RJ45 connectors are provided on the1407-CGCM-DLR unit. Use the thumbwheel switches on the front of the CGCM unit to set the EtherNet/IP network IP address . The two thumbwheel-switches set the last two digits of the 192.168.1.1xy static IP address.
  • Page 39: Cgcm-Dlr Unit Operation

    Chapter CGCM-DLR Unit Operation This section provides an operational description of the functions of the CGCM-DLR unit. The CGCM-DLR unit incorporates the following to provide the regulation, synchronizing, and protection functions that are described in this section: • Hardware inputs and outputs •...
  • Page 40 Chapter 3 CGCM-DLR Unit Operation Figure 27 - Simplified Block Diagram Memory Circuits Flash EEPROM Memory Watch-dog Open Timer Collector Outputs RD RLY VREF (+) Auxiliary Load LS (+) VREF (-) Input Sharing LS (-) COM0 Factory Test Port Remote EX-D (+) Commun- Microprocessor...
  • Page 41: Inputs And Outputs

    CGCM-DLR Unit Operation Chapter 3 Inputs and Outputs Figure 28 shows the front panel layout of the CGCM-DLR unit. Input and output connections are made through the terminal blocks TB1…TB7. Figure 28 - Front Panel Layout IP ADDRESS 192.168.1.1XY 00-87, 89-98 RESTORE FACTORY DEFAULTS...
  • Page 42: Analog Inputs

    Chapter 3 CGCM-DLR Unit Operation Analog Inputs The CGCM-DLR unit provides a number of analog inputs for use in the regulation and control of standalone and paralleled generator systems. The following sections outline each of the inputs. Generator Voltage Sensing Inputs The CGCM-DLR unit senses generator voltage through voltage transformers (VTs) installed across the generator output leads.
  • Page 43: Power Inputs

    CGCM-DLR Unit Operation Chapter 3 Cross-current The CGCM-DLR unit senses reactive differential current through properly connected current transformers that are typically installed on the B-phase output leads of each paralleled generator. Typical Cross-current CT Locations and Polarity page 36 for more information.
  • Page 44: Discrete Inputs - Remote Excitation Enable

    Chapter 3 CGCM-DLR Unit Operation Discrete Inputs - Remote Excitation Enable The remote excitation enable input is a 24V DC input. When 24V DC is applied to the input, CGCM-DLR unit excitation is permitted. For generator excitation to occur, excitation must be enabled in software, IMPORTANT ®...
  • Page 45: Discrete Outputs

    CGCM-DLR Unit Operation Chapter 3 Real-power Load Sharing Real-power load sharing terminals are provided to allow two or more CGCM-DLR units or other compatible generator control devices (such as the Line Synchronization Module™, catalog number 1402-LSM) to load the generators under their control such that the same per unit output is developed by each generator.
  • Page 46: Com 1 Redundancy Port

    Chapter 3 CGCM-DLR Unit Operation Com 1 Redundancy Port The redundancy port lets one CGCM-DLR unit communicate with its partner CGCM-DLR unit in a redundant system, which lets the partner unit auto-track the primary unit control modes. EtherNet/IP Network Port The EtherNet/IP DLR network ports are used to interface with a Logix family programmable logic controller.
  • Page 47: Operational Functions

    CGCM-DLR Unit Operation Chapter 3 Operational Functions The following sections describe the operational functions of the CGCM-DLR unit. The functions include the following: • Excitation Control Modes • Limiting Functions • Protection Functions • Synchronizing • Real-power Load Sharing • Metering •...
  • Page 48 Chapter 3 CGCM-DLR Unit Operation Gains The CGCM-DLR unit regulates excitation current by using a proportional, integral, and derivative (PID) control algorithm. Your gain settings determine the regulator response of the CGCM-DLR unit. The gains for each mode include the following: •...
  • Page 49 CGCM-DLR Unit Operation Chapter 3 Droop (reactive current compensation) Droop (reactive current compensation) is a method of controlling reactive current when a generator is connected in parallel with another energy source. Droop adjusts the generator voltage in proportion to the measured generator reactive power.
  • Page 50 Chapter 3 CGCM-DLR Unit Operation To activate cross-current compensation, you must do the following: • Connect the generators in parallel. • Connect the cross-current CT and generator VTs. • Write the desired cross-current gain to the CrossCurrentGain tag. • Enable excitation (tag SoftwareExcEn = 1). •...
  • Page 51 CGCM-DLR Unit Operation Chapter 3 Power Factor Regulation Mode (PF) In PF mode, the CGCM-DLR unit controls field excitation current output to maintain the commanded power factor setpoint. The CGCM-DLR unit uses the measured generator voltages and currents to calculate power factor. The PF feedback loop includes adjustable proportional and integral gains.
  • Page 52 Chapter 3 CGCM-DLR Unit Operation Soft Start Mode CGCM-DLR unit Soft Start mode provides for an orderly build-up of generator voltage from residual to the voltage setpoint in the desired time with minimal overshoot. When the system is in Soft Start mode, the CGCM-DLR unit adjusts the voltage reference that is based on the Soft Start Initial Voltage and Soft Start Time.
  • Page 53 CGCM-DLR Unit Operation Chapter 3 Internal Tracking The CGCM-DLR unit provides a tracking function between the non-active modes of operation and the active mode of operation. This function minimizes the potential for instability that can occur when switching from one mode to another.
  • Page 54: Limiting Functions

    Chapter 3 CGCM-DLR Unit Operation Limiting Functions This section discusses the different types of limiting functions the CGCM-DLR unit provides. • Volts/Hertz Limit • Over-excitation Limit • Under-excitation Limit Generator Capability Curve The generator capability curve graphically depicts the combinations of real and reactive power a generator is able to produce (or absorb, in the case of reactive power) without damage that is caused by overheating.
  • Page 55 CGCM-DLR Unit Operation Chapter 3 Volts/Hertz Limit The Volts/Hertz limit acts to reduce the generator output voltage by an amount proportional to generator frequency. Generator output voltage reduction is done to help protect the generator from overheating and reduce the impact on the prime mover when adding a large load.
  • Page 56 Chapter 3 CGCM-DLR Unit Operation Over-excitation Limit The Over-excitation limit (OEL) operates in all modes except FCR. The CGCM-DLR unit senses and limits the field current to prevent field overheating. When the limit is reached, the limiter function overrides AVR, VAR, or Power Factor modes to limit field current to the preset level.
  • Page 57 CGCM-DLR Unit Operation Chapter 3 Three OEL current levels, high, medium, and low are defined for online operation as shown in Figure 33. The high and medium current levels can be maintained only for time periods you define. The generator can operate continuously at or below the low OEL current level.
  • Page 58 Chapter 3 CGCM-DLR Unit Operation Under-excitation Limit The Under-excitation limit (UEL) operates in all modes except FCR mode. UEL senses the leading VAR input of the generator and limits any further decrease in excitation to prevent loss of synchronization and the excessive end-iron heating during parallel operation.
  • Page 59: Protection Functions

    CGCM-DLR Unit Operation Chapter 3 Protection Functions The CGCM-DLR unit detects the fault conditions that are listed and described in the following section. Faults that are detected by the CGCM-DLR unit are communicated to the host Logix programmable controller. Fault flags are communicated in the Scheduled Read table.
  • Page 60 Chapter 3 CGCM-DLR Unit Operation Over-excitation Voltage (59F) (field over-voltage) When the field voltage rises above the level you specified for more than a set amount of time, a field over-voltage annunciation occurs. Once the field voltage drops below the threshold, the field over-voltage timer is reset. If this fault occurs, the CGCM-DLR unit shuts down excitation and sets tag OvrExcFlt = 1 in the Scheduled Read table.
  • Page 61 CGCM-DLR Unit Operation Chapter 3 Loss of Sensing (60FL) For three-wire and four-wire sensing, Loss of Sensing detection is based on the logical combination of several conditions. They include these conditions: 1. The average positive sequence voltage is greater than 8.8% of the AVR setpoint.
  • Page 62 Chapter 3 CGCM-DLR Unit Operation Loss of Excitation Power (PMG) (27) If voltage to the PMG excitation power inputs falls below 10V AC for approximately 400 ms or more, a Loss of Excitation power fault occurs. When single phase PMG is selected, the CGCM-DLR unit senses phases A and C for this function.
  • Page 63 CGCM-DLR Unit Operation Chapter 3 Over-frequency (81O) When generator frequency exceeds the over-frequency setpoint for a specified amount of time, a definite time over-frequency fault occurs. Once the frequency drops below the threshold, the over-frequency fault timer is reset. If this fault occurs, tag OvrFreqFlt = 1 in the Scheduled Read table.
  • Page 64: Synchronizing

    Chapter 3 CGCM-DLR Unit Operation When the ripple current at one of these frequencies exceeds the applicable user specified threshold, a timer is started. Once the time delay is exceeded, a rotating diode fault occurs. If the ripple current falls below the threshold (configured as percent of measured excitation current) before the timer expires, the timer is reset.
  • Page 65 CGCM-DLR Unit Operation Chapter 3 When synchronizing a system between systems with differing metering configurations, the synchronization configuration must account for any phase shift or voltage differences between the two systems. For example, when synchronizing a three-wire (delta) generator to four-wire (Wye) bus system, the synchronization configuration must account for the 30°...
  • Page 66 Chapter 3 CGCM-DLR Unit Operation • Single-phase The CGCM-DLR unit can synchronize where only one line-to-line input is available from the generator or bus. This scheme is the case for single-phase systems or in systems where only one phase has a transformer that is connected for synchronization purposes.
  • Page 67 CGCM-DLR Unit Operation Chapter 3 – Phase rotation (3-phase connection only): If the bus and generator are opposite in phase rotation, synchronization fails. The CGCM-DLR unit continually checks phase rotation match when synchronization is active. • Permissive Synchronization The host controller sets the PermissiveSyncEn tag to enable Permissive Synchronization mode.
  • Page 68: Real-Power Load Sharing

    Chapter 3 CGCM-DLR Unit Operation Synchronizing Control Software Interface When synchronization is active, the CGCM-DLR unit adjusts the values of the Scheduled Read table tags as described in the following section: • Voltage Match Error as computed • Frequency Match Error as computed •...
  • Page 69: Metering

    CGCM-DLR Unit Operation Chapter 3 Limit defines the maximum per unit load share error reported to the host controller. Rate defines the maximum change in the load share error per CGCM-DLR unit update cycle, expressed in percent of rated kilowatts per second. For example, if a change of load of 50% is required and the rate set for 10% per second, the change takes 5 seconds to complete.
  • Page 70 Chapter 3 CGCM-DLR Unit Operation Metered Parameters The CGCM-DLR unit provides the following metered parameters. The collection of metering data is dependent on the metering wiring mode that is selected, for example, single-phase, open-delta, four-wire wye, and three-wire wye. Table 3 - Metered Parameter Accuracy Metered Parameter Metering Wiring Mode Single-phase...
  • Page 71: Redundancy

    CGCM-DLR Unit Operation Chapter 3 Figure 36 - Power System Sign Conventions Forward Reactive Power Flow (export) watts negative (-) watts positive (+) vars positive (+) vars positive (+) power factor lagging (+) power factor lagging (+) Forward Real Power Flow Reverse Real Power Flow (export) (import)
  • Page 72 Chapter 3 CGCM-DLR Unit Operation If a loss of communication between redundant CGCM-DLR units occurs, the primary CGCM-DLR unit remains primary and the secondary CGCM-DLR unit switches to primary also. Because in this state both units are supplying current to the field, the host Logix programmable controller must be programmed to take corrective action when this condition occurs.
  • Page 73 CGCM-DLR Unit Operation Chapter 3 Once the host controller establishes primary and secondary CGCM-DLR unit roles, they remain in their respective modes indefinitely. You can force a transfer by disabling excitation on the primary unit. The disabling of excitation causes the secondary unit to sense a loss of tracking information, switch to Primary mode, and take over-excitation control.
  • Page 74: Watchdog Timer

    Chapter 3 CGCM-DLR Unit Operation The redundant tracking delay setting adjusts the delay of the tracking function to prevent the secondary CGCM-DLR unit output from being adjusted into an undesirable condition. For example, with AVR mode active in the primary CGCM-DLR unit, if the generator sensing VT fails open the excitation output goes to a full-on state.
  • Page 75: Cgcm-Dlr Unit Configuration

    Chapter CGCM-DLR Unit Configuration Introduction This section provides a generic set-up and verification procedure for power generation systems by using the CGCM-DLR unit and the Logix Designer application. The various configuration parameters that are required to customize the device to a specific application are presented. Because every application is unique, read this section carefully and make sure that the configuration entries are appropriate for the system being implemented.
  • Page 76: Record System Parameters

    Follow these steps to create a module in the ControlLogix controller with Studio 5000 Logix Designer® application, version 20 or later. the ControlLogix Controller The 1407-CGCM-DLR module uses an Add-on Profile (AOP). If not already IMPORTANT installed, install the Add-on Profile. See Appendix G, page 255).
  • Page 77 CGCM-DLR Unit Configuration Chapter 4 In this example, the address of the controller Ethernet communication module is 192.168.1.111, and the CGCM-DLR address is 192.168.1.114. The Logix Designer application must be offline when you create a IMPORTANT CGCM-DLR module. 1. Open Logix Designer application. 2.
  • Page 78 Chapter 4 CGCM-DLR Unit Configuration 4. Under the I/O Configuration tree, right-click on 1756 Backplane, and choose New Module. The Select Module Type dialog box appears. 5. Choose an EtherNet/IP® DLR communication module and click Create. The New Module configuration dialog box appears. 6.
  • Page 79 7. Under I/O Configuration, right-click the 1756-EN2TR EtherNet/IP DLR module, and choose New Module from the menu. The Select Module Type dialog box appears. 8. Select the 1407-CGCM-DLR Combination Generator Control Module 2 Port from the list in the Catalog tab. 9. Click Create.
  • Page 80 Chapter 4 CGCM-DLR Unit Configuration 10. Enter the following information for the new module: a. Name: must be compliant with IEC-1131-3. b. IP address: if you have set the IP address by using the thumbwheel switches to 00-87 or 89-98, then select the Private Network checkbox. c.
  • Page 81: Electronic Keying

    CGCM-DLR IP address is changed from 192.168.1.114 to 10.90.172.72. This procedure is performed in the Logix Designer application and assumes the following: • The 1407-CGCM-DLR module has previously been created (see Create the New 1407-CGCM-DLR Module in the I/O Configuration on page 76).
  • Page 82 Chapter 4 CGCM-DLR Unit Configuration To configure manually a static IP address, follow these steps. 1. Open the Module Properties and navigate to the Connection tab. 2. Check the Inhibit Module checkbox and click Apply. The Connection Interruption dialog box appears. 3.
  • Page 83 CGCM-DLR Unit Configuration Chapter 4 4. In the Module Properties dialog box, click Internet Protocol. 5. Select 'Manually configure IP settings' under Internet Protocol (IP) Settings. If the option to select 'Manually configure IP settings' is grayed out, IMPORTANT verify that the thumbwheel switches on the CGCM-DLR unit have been set to 99 and the unit has been power-cycled.
  • Page 84 Chapter 4 CGCM-DLR Unit Configuration The Connection Interruption dialog box appears. 8. To apply changes, click Yes. An Invalid Path dialog box appears. 9. Click OK. 10. To close the Module Properties window, click OK. 11. Click Go Offline with the controller. Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 85 CGCM-DLR Unit Configuration Chapter 4 12. Open the Module Properties of the CGCM-DLR unit. 13. In the General tab of Module Properties, update the IP address field to match the IP address that is configured in Step 14. Then, click Apply. In this example, the IP address was updated from 192.168.1.114 to 10.90.172.72.
  • Page 86 Chapter 4 CGCM-DLR Unit Configuration 16. Go Online with the controller. 17. Click Download in the prompt. Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 87: Device Setup

    CGCM-DLR Unit Configuration Chapter 4 18. Click Download to confirm. The IP address of the CGCM-DLR unit has now been successfully configured. To use the controller in this example on the Enterprise network, IMPORTANT readdress the controller with the CGCM-DLR unit. Or, use another controller that is already on the Enterprise network.
  • Page 88: Applying The Configuration To The Cgcm Unit

    Chapter 4 CGCM-DLR Unit Configuration Applying the Configuration to the CGCM Unit The Module Properties configuration pages provide a simple way for you to enter and edit CGCM-DLR unit configuration parameters. Changes that you make to the configuration are not always immediately sent to the unit. The configuration data is stored in two controller tags in the ControlLogix controller, the Configuration tag and the Unscheduled Write tag.
  • Page 89 CGCM-DLR Unit Configuration Chapter 4 The Logix Designer application performs configuration data checks as specified by the limits that are shown in the data tables. The data checks verify that the entry is within range for the device, however, it does not verify that it is reasonable for the application.
  • Page 90 Chapter 4 CGCM-DLR Unit Configuration Generator Page The Generator page is used to configure the unit to the design ratings of the generator. Enter the generator nameplate ratings in the appropriate fields of the Generator page. Rated Frequency - Sets the generator rated frequency in Hz. Sets the value of tag GenRatedFreq in the Configuration table.
  • Page 91 CGCM-DLR Unit Configuration Chapter 4 Transformers Page The Transformers page is used to match the unit with the configuration of the generator voltage and current sensing transformers. To configure the Transformer page, you must know the system wiring configuration. The settings that are entered on the Transformers page must correspond to the actual wiring configuration.
  • Page 92 Chapter 4 CGCM-DLR Unit Configuration • Bus VT Configuration - The bus VT configuration selections are (1) single-phase, (2) two-transformer open delta, (3) three-wire Wye, (4) four-wire Wye, and (5) dual breaker. This parameter is stored in the tag BusVT_Config in the configuration table. For applications that require synchronization to one of two busses, dual breaker must be selected.
  • Page 93 CGCM-DLR Unit Configuration Chapter 4 Excitation Page The Excitation page is used to configure the unit settings that are related to operation and protection of the exciter. • Soft Start Initial Voltage - The generator voltage setpoint that is applied immediately after enabling the CGCM-DLR unit excitation output.
  • Page 94 Chapter 4 CGCM-DLR Unit Configuration • Loss of Excitation Current setpoint - Establishes the level of excitation current that is considered to be a minimum that is required to maintain generator synchronization when in parallel with other power sources such as a utility grid.
  • Page 95 CGCM-DLR Unit Configuration Chapter 4 Volts/Hz Page The Volts/Hz page is used to configure the unit settings that are related to operation of the Volts/Hz compensation function. The parameters define a curve, which determines the Volts/Hz response. • Volts per Hertz Upper Knee Frequency - Establishes the frequency at which the V/Hz characteristic starts to reduce the generator voltage as a function of generator frequency.
  • Page 96 Chapter 4 CGCM-DLR Unit Configuration • Volts per Hertz Lower Slope - Establishes the rate at which the V/Hz characteristic reduces the generator voltage as a function of generator frequency below the Lower Knee Frequency setting. Tag VperHz_LoSlope in the configuration table stores this value, expressed as a number that reflects per unit change in voltage for each per unit change in frequency.
  • Page 97 CGCM-DLR Unit Configuration Chapter 4 • Over-excitation Limiting Enable – Select this checkbox to enable over-excitation limiting, which sets the OEL_En tag in the configuration table. Tag OEL_En in the configuration table stores this parameter. The OEL_En tag in the Output (Scheduled Write) Data table must also be set to enable this function.
  • Page 98 Chapter 4 CGCM-DLR Unit Configuration Related Parameters • GenRatedExcI • OEL_En tag in the Output table UEL Page The UEL tab is used to configure the unit settings that are related to operation of the Under-excitation Limiting (UEL) function. The values that are entered in this tab establish break points in a piecewise linear curve that defines the characteristic curve for this function.
  • Page 99 CGCM-DLR Unit Configuration Chapter 4 • The following tags determine the points that are shown in this UEL configuration diagram. These tags are in the configuration table and are set by the like-named fields on the UEL page. VAR values are negative, which indicate leading.
  • Page 100 Chapter 4 CGCM-DLR Unit Configuration Gain Page The Gain page is used to configure the unit gain parameters necessary for the operation of the excitation control. Except as otherwise noted, gain parameters are unitless. Appendix B provides additional information regarding the mathematical models that are used in the unit.
  • Page 101 CGCM-DLR Unit Configuration Chapter 4 • Proportional Gain Kp - Sets the proportional gain, which determines the characteristic of the dynamic response to changes in generator voltage. If the transient response has too much overshoot, decrease Kp. If the transient response is too slow, with little or no overshoot, then increase Kp. The tag AVR_FCR_Kp in the Unscheduled Write table stores this parameter.
  • Page 102 Chapter 4 CGCM-DLR Unit Configuration VAR Control The VAR Control gains determine the response of the VAR control loop for the voltage regulation function when in VAR mode. These settings can be adjusted during system startup. Chapter 5 for more information on tuning the VAR control gains. •...
  • Page 103 CGCM-DLR Unit Configuration Chapter 4 Other Gains The remaining three gains are stored in the Configuration table and can only be written to the CGCM-DLR unit when excitation is disabled. Chapter 6 for more information. • AVR/FCR Control Auxiliary Gain - Sets the influence of the auxiliary input on the AVR/FCR operating setpoint.
  • Page 104 Chapter 4 CGCM-DLR Unit Configuration Tracking Page The Tracking page is used to configure the unit internal and redundant tracking parameters. Enter the internal tracking, redundant tracking, and traverse rates in the appropriate fields of the Tracking page. Internal Tracking •...
  • Page 105 CGCM-DLR Unit Configuration Chapter 4 An example of how these parameters affect tracking is shown in the Internal Tracking graph. In this example, a loss of sensing causes a full-scale regulator output. The internal tracking delay permits FCR mode to begin operation at the output level before the loss of sensing.
  • Page 106 Chapter 4 CGCM-DLR Unit Configuration • Redundant Tracking Delay - This setting adjusts the delay in the redundant tracking function. The value of the RedndtTrackDelay tag in the Configuration table, expressed in seconds, is set. Its purpose is to reduce the likelihood that the short-term response of the active CGCM-DLR unit Regulating mode to an upset is transferred to the back-up CGCM-DLR unit when it becomes primary.
  • Page 107 CGCM-DLR Unit Configuration Chapter 4 The following diagram shows the function of internal tracking and traverse rates on a switch from VAR to PF operating modes. Figure 40 - Internal Tracking and Traverse Rates Generator Voltage PF Mode Internal PF Mode Traverse Rate Tracking Setpoint = Determines Transition to New Measured PF...
  • Page 108 Chapter 4 CGCM-DLR Unit Configuration Synch Page The Synch tab is used to configure the unit parameters that are related to the synchronizing function of the CGCM-DLR unit. Synchronization Limits • Frequency Match - Establishes the acceptance window for frequency matching, which is defined by Configuration table tags SyncFreqLoLimit and SyncFreqHiLimit.
  • Page 109 CGCM-DLR Unit Configuration Chapter 4 Bus A Offsets • Voltage multiplier - Establishes a factor by which the Bus A voltage is scaled during synchronization. It can be used to compensate for transformer ratio differences between the generator and bus voltages. For example, if the generator nominal voltage is 4160V and the nominal Bus A voltage is 12,480V (each measured line-to-line), a voltage multiplier value of 0.333 permits voltage matching during synchronization.
  • Page 110 Chapter 4 CGCM-DLR Unit Configuration Table 4 provides a guide for how to adjust phase offset for wiring IMPORTANT configurations that are shown in Chapter 2, Installation. Other wiring configurations are possible. It is your responsibility to determine and verify phase offset values for wiring configurations that are not depicted in this manual.
  • Page 111 CGCM-DLR Unit Configuration Chapter 4 Related Parameters • GenVT_Config • BusVT_Config • GenRated_V Load Share Page The Load Share page is used to configure the unit parameters that are related to the real power load-sharing function of the unit. • Full Scale Voltage - Sets the load share output voltage when the generator is producing rated real power.
  • Page 112 Chapter 4 CGCM-DLR Unit Configuration Voltage Page The Voltage page is used to configure the unit parameters that are related to the voltage protection and compensation functions. Overvoltage • Setpoint - Establishes the overvoltage setpoint. This setpoint is stored in tag Ovr_V_Setpt in the configuration table and scaled in per cent rated generator volts.
  • Page 113 CGCM-DLR Unit Configuration Chapter 4 Undervoltage • Setpoint - Establishes the undervoltage setpoint. This setpoint is stored in tag Undr_V_Setpt in the configuration table and scaled in per cent rated generator volts. • Delay - Establishes the time the generator voltage must be below the undervoltage setpoint before the unit annunciates an undervoltage fault.
  • Page 114 Chapter 4 CGCM-DLR Unit Configuration Current Page The Current page is used to configure the parameters that are related to the over-current protection function. Appendix A for more information on setting the parameters in the Current tab and the available time over-current characteristic curves. Over-current •...
  • Page 115 CGCM-DLR Unit Configuration Chapter 4 • Validate and graph button – Updates the graph that is shown on the Current tab to display the selected over-current characteristic curve. The specific curve that is selected by the over-current time dial setting is displayed in black.
  • Page 116 Chapter 4 CGCM-DLR Unit Configuration • Under-frequency Delay - Establishes the amount of time in seconds that the frequency must be below the under-frequency setpoint before the unit annunciates the fault. This parameter is stored in tag UndrFreqTimeDly in the configuration table. Related Parameters •...
  • Page 117 CGCM-DLR Unit Configuration Chapter 4 • Reverse kVAR Fault Delay - establishes the amount of time in seconds that the reverse kVAR must be above the reverse kVAR setpoint before the unit annunciates the fault. This parameter is stored in tag Rev_kVAR_TimeDly in the configuration table.
  • Page 118 Chapter 4 CGCM-DLR Unit Configuration Fault Relay Page The Fault Relay page is used to configure the unit parameters that are related to the fault relay output. Check the box to enable the fault output for that particular fault. The fault output relay operates when a selected fault occurs if the fault output is enabled, and the corresponding fault tag in the Output (Scheduled Write) Data table is set.
  • Page 119: Cgcm-Dlr Unit Startup

    Chapter CGCM-DLR Unit Startup Introduction This chapter provides a suggested set of steps to follow when you commission a CGCM-DLR system. The following tasks must be completed before you setup a CGCM-DLR system: • Evaluated the system design needs. • Selected a suitable instrument wiring arrangement. •...
  • Page 120: Recommended Equipment

    Chapter 5 CGCM-DLR Unit Startup ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors. Follow these guidelines when you handle the module. Touch a grounded object to discharge static potential. • Wear an approved wrist strap-grounding device. • Do not open the module or attempt to service internal components. •...
  • Page 121: Test Current And Voltage Source

    CGCM-DLR Unit Startup Chapter 5 Test Current and Voltage Source An appropriately calibrated 3-phase voltage and 3-phase current source is recommended to simulate generator and system power conditions at known operating points of interest. These sources can be connected to the VT and CT input terminals in place of system VT and CT instruments.
  • Page 122: Verify The Network Connection

    Chapter 5 CGCM-DLR Unit Startup Verify the Network Connection Follow these steps to verify the network connection. 1. To browse and confirm that the CGCM-DLR unit is on the EtherNet/IP network, use the RSWho function of RSLinx software. 2. Verify the unit firmware revision is the same or later than indicated on the firmware revision label.
  • Page 123: Simulate Ac Gen And Bus Inputs And Verify Metered

    CGCM-DLR Unit Startup Chapter 5 Simulate AC Gen and Bus Inputs and Verify Metered Parameters Follow these steps to simulate the AC Gen and Bus inputs and verify the metered parameters. 1. Disconnect Generator VT and CT inputs, and Bus VT inputs, in a manner that lets you verify as much of the system wiring as practical.
  • Page 124 Chapter 5 CGCM-DLR Unit Startup Over-excitation Voltage (59F) Follow these steps to test that the Over-excitation voltage function is working properly. 1. Connect a suitable load to the excitation output terminals of the CGCM-DLR unit. 2. Decrease the field over-excitation voltage setpoint to a level that causes an alarm.
  • Page 125 CGCM-DLR Unit Startup Chapter 5 Generator Undervoltage (27) Follow these steps to test that the Generator undervoltage function is working properly. 1. Connect a suitable load to the excitation output terminals of the CGCM-DLR unit. 2. Increase the generator undervoltage setpoint to a level that causes an alarm. 3.
  • Page 126 Chapter 5 CGCM-DLR Unit Startup Loss of Permanent Magnet Generator (PMG/Excitation Power) (27) This fault is enabled only when PMG excitation is selected and excitation is enabled. If shunt excitation is selected, skip these steps. Follow these steps to test that the Loss of Permanent Magnet Generator function is working properly.
  • Page 127 CGCM-DLR Unit Startup Chapter 5 Under-frequency (81U) Follow these steps to test that the Under-frequency function is working properly. 1. Connect a suitable load to the excitation output terminals of the CGCM-DLR unit. 2. Enable excitation in FCR mode. 3. Clear the EngineIdle tag in the controller tag database. 4.
  • Page 128 Chapter 5 CGCM-DLR Unit Startup Phase Rotation Error (47) Follow these steps to test that the Phase Rotation Error function is working properly. 1. Apply simulated generator voltage signals by using the test voltage source, opposite to the configured phase rotation. 2.
  • Page 129: Operational Testing Of The Cgcm-Dlr Unit Functions

    CGCM-DLR Unit Startup Chapter 5 Operational Testing of the CGCM-DLR Unit Functions These tests can be performed to verify the applicable operational functions of the CGCM-DLR unit. These tests are performed with the generator and prime mover fully functional. These steps are assumed to be performed in order, so that the conditions at the end of one step exist at the beginning of the next step.
  • Page 130 Chapter 5 CGCM-DLR Unit Startup Verify and Adjust FCR Operation Follow these steps to verify and adjust the FCR operation. 1. Select the FCR mode of operation. 2. Set the FCR setpoint to the generator manufacturer specified no-load exciter field current. 3.
  • Page 131: Test Synchronization

    CGCM-DLR Unit Startup Chapter 5 Verify and Adjust AVR Mode Operation (constant voltage) Follow these steps to verify and adjust the AVR mode operation. 1. Adjust the AVR setpoint to the generator rated voltage. 2. Select Constant Voltage mode by disabling reactive compensation (droop). 3.
  • Page 132: Verify Applicable Automatic Operating Modes

    Chapter 5 CGCM-DLR Unit Startup Generator Breaker in Test Position Follow these steps to test synchronization when the generator breaker is in the test position. 1. Verify the generator main circuit breaker is in a test position that prevents the breaker from closing when the CGCM-DLR unit issues a close command.
  • Page 133 CGCM-DLR Unit Startup Chapter 5 Droop (reactive current compensation) Operation Perform this test with the generator operating in parallel with a large power source that is maintaining constant voltage. You could also use one or more additional generators. Follow these steps to test Droop operation. 1.
  • Page 134 Chapter 5 CGCM-DLR Unit Startup VAR Control Perform this test with the generator operating in parallel with a large power source that is maintaining constant voltage. Follow these steps to test the VAR control operation. 1. Place the voltage control in Droop mode. 2.
  • Page 135 CGCM-DLR Unit Startup Chapter 5 PF Control Perform this test with the generator operating in parallel with a large power source that is maintaining constant voltage. Follow these steps to test the PF control operation. 1. Place the voltage control in Droop mode. 2.
  • Page 136: Verify Operation Of Limiter Functions And Diode Monitor

    Chapter 5 CGCM-DLR Unit Startup Verify Operation of Limiter Functions and Diode Monitor Perform the following tests to verify Limiter Functions and Diode Monitor operation. Volts/Hz Operation Perform this test with the generator operating unloaded in Constant Speed mode and constant voltage AVR mode. Follow these steps to test the Volts/Hz operation.
  • Page 137 CGCM-DLR Unit Startup Chapter 5 Over-excitation Limiting (OEL) Operation Perform this test with the generator operating unloaded in Constant Speed mode and constant voltage AVR mode. Follow these steps to test the OEL operation. 1. Enable the OEL function. 2. Determine the field current that is required to reach 105% of the rated generator voltage.
  • Page 138: Document Configuration Parameter And Wiring Changes

    Chapter 5 CGCM-DLR Unit Startup 5. Set the Shorted Diode Level to a value that is 50 times the highest normal percent ripple that is found earlier. The multiplier can be varied from 40…70 to adjust the trip margin. Regardless of the calculated value, the level has a maximum value of 70. A reduction of the multiplier can result in nuisance EDM shorted diode indications.
  • Page 139: Introduction

    Chapter CGCM-DLR Unit Software Interface Introduction This chapter provides information on communication with the CGCM-DLR unit by using the EtherNet/IP® Device Level Ring (DLR) network. It discusses scheduled and unscheduled messaging between a ControlLogix® controller and the CGCM-DLR unit and touches briefly on the user program communication interface.
  • Page 140: Cgcm-Dlr Unit User Program Interface

    Chapter 6 CGCM-DLR Unit Software Interface CGCM-DLR Unit User Program The CGCM-DLR unit and the ControlLogix controller transfer data through five controller tags that are based on the module-defined data types that are listed Interface in the Summary of Data Tables.
  • Page 141: Configuration Messaging

    Unscheduled Write data table to the CGCM-DLR unit. Simplified logic rung to send the Unscheduled Write message from the controller to the 1407-CGCM-DLR after the Configuration write has been accepted. Enable_UW is a user-defined permissive interlock. CGCM:I.ConfigRcvd asserted indicates that the CGCM has accepted the scheduled Configuration write.
  • Page 142 Chapter 6 CGCM-DLR Unit Software Interface Connection Behavior During Configuration The CGCM-DLR unit operates with an active Class 1 connection with a ControlLogix programmable controller that you have programmed and configured. The Class 1 connection is made through the Add-on Profile. The CGCM-DLR unit controls the state of 2 bits in the Input data table to interact with the controller during configuration: •...
  • Page 143: Operating Interfaces

    CGCM-DLR Unit Software Interface Chapter 6 Configuration Summary • The CGCM-DLR unit accepts Configuration data only when excitation is disabled and all configuration data is in the correct range. • The CGCM-DLR unit accepts Unscheduled Write data regardless of the excitation state provide that all Unscheduled Write data is in the correct range.
  • Page 144: Cgcm-Dlr Unit Data Tables

    Chapter 6 CGCM-DLR Unit Software Interface CGCM-DLR Unit Data Tables The tables in this section show the content and organization of the CGCM- DLR Unit data tables. Terms These terms are used in the following tables: • Spare - Unused now, can be available for future use. If read, spares are zero value.
  • Page 145: Assembly Object Properties

    CGCM-DLR Unit Software Interface Chapter 6 Abbreviation Definition Abbreviation Definition Current Under-excitation Limiting Init Initial Undr Under Kilo Unschd Unscheduled Derivative gain Voltage Overall gain Volt amps Integral gain Volt amps Reactive Proportional gain VT (or PT) Voltage (Potential) Transformer Limit Watt Assembly Object Properties...
  • Page 146 Chapter 6 CGCM-DLR Unit Software Interface Table 7 - Scheduled Read Data Table Byte Size in Type Bits Tag Name Description-+ Units Range Bytes DINT 0…7 Status_32_bit Connect Status BOOL RevVARFlt Reverse kVAR Fault 0=Inactive, 1=Active BOOL RevPwrFlt Reverse kW Fault BOOL OvrExcFlt Over-excitation Fault...
  • Page 147 CGCM-DLR Unit Software Interface Chapter 6 Table 7 - Scheduled Read Data Table Byte Size in Type Bits Tag Name Description-+ Units Range Bytes BOOL Activebus_A_B Bus A/B Active 0=Bus A, 1=Bus B BOOL Raise_V Raise Voltage 0=False, 1=True BOOL Lower_V Lower Voltage BOOL...
  • Page 148 Chapter 6 CGCM-DLR Unit Software Interface Table 7 - Scheduled Read Data Table Byte Size in Type Bits Tag Name Description-+ Units Range Bytes Real kW_AnalogPU_Load kW Analog Value Per Unit 0…1 Real kVAR_LS_InputV kVAR Load Share Input Voltage Volts 0…1 Real kVAR_PU_load...
  • Page 149: Output (Scheduled Write) Data Table

    CGCM-DLR Unit Software Interface Chapter 6 Output (scheduled write) Data Table The Output data table contains time-critical command and setpoint data that is written to the CGCM-DLR unit by the ControlLogix controller. The host controller automatically writes the data in this Controller Tag to the unit at the scheduled update rate whenever a connection between the two exists.
  • Page 150 Chapter 6 CGCM-DLR Unit Software Interface Data Table Table 10 - Output (scheduled write) Data Table, Assembly Instance 1 Byte Size in Type Bits Tag Name Description Units Range Bytes BOOL RevVARFltOutEn Reverse VAR Fault Output Enable 0 = Disabled, 1 = Enabled BOOL RevPwrFltOutEn...
  • Page 151 CGCM-DLR Unit Software Interface Chapter 6 Table 10 - Output (scheduled write) Data Table, Assembly Instance 1 Byte Size in Type Bits Tag Name Description Units Range Bytes BOOL Set_kW_Hrs Set/Clear kW Hours 0 = De-assert, 1 = Assert BOOL Set_kVAR_Hrs Set/Clear kVAR Hours BOOL...
  • Page 152: Unscheduled Read Data Table

    Chapter 6 CGCM-DLR Unit Software Interface Unscheduled Read Data Table The Unscheduled Read data table contains metering and other non time-critical status data that is read from the CGCM-DLR unit by the ControlLogix controller. The host controller reads the data in this Controller Tag from the unit by using unscheduled messaging that is controlled by the user program.
  • Page 153 CGCM-DLR Unit Software Interface Chapter 6 For instance, a 30 MVA machine operating at 10% load yields an energy tag limit (8,338,600 * 0.1 * 30000) = 25,015,800,000 kVAh, or 2.50158 x 10 kVAh When the energy tag value exceeds 8,338,600, rounding of the value begins to occur.
  • Page 154: Unscheduled Write Data Table

    Chapter 6 CGCM-DLR Unit Software Interface Table 12 - Unscheduled Read Data Table, Assembly Instance 5 Byte Size in Type Tag Name Description Units Range Bytes Real PhAB_GenV Phase AB Generator Voltage 0…30,000 Real PhBC_GenV Phase BC Generator Voltage Real PhCA_GenV Phase CA Generator Voltage Real...
  • Page 155 CGCM-DLR Unit Software Interface Chapter 6 Assembly Object Instance 6 - Unscheduled Write Data Table The Get Attributes Single service for instance 6 of the Assembly Object can access the following information. Table 13 - Get Attributes Single (Service Code 0x0E) Name Attribute ID Data Type...
  • Page 156 Chapter 6 CGCM-DLR Unit Software Interface Data Table The Unscheduled Write tag is appended to the Configuration tag in the Logix controller tags. If desired, the Unscheduled Write must be read back from the CGCM-DLR unit by an explicit message to a tag that you created with module- defined data type AB:1407_CGCM_Unscheduled_Write3.
  • Page 157: Configuration Data Table

    CGCM-DLR Unit Software Interface Chapter 6 Configuration Data Table The Configuration data table contains configuration parameters. The parameters are automatically written to the CGCM-DLR unit by the ControlLogix controller when either of the following is completed: • A connection is first established (Forward Open) •...
  • Page 158 Chapter 6 CGCM-DLR Unit Software Interface The Set Attributes Single service for instance 4 of the Assembly Object can access the following information. Table 17 - Set Attributes Single (Service Code 0x10) Name Attribute ID Data Type Value Data UINT See Unscheduled Configuration Read/ Write Data Table, Assembly Instance 4 Use of this service is not recommended.
  • Page 159 CGCM-DLR Unit Software Interface Chapter 6 Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4 Byte Size in Type Bits Tag Name Description Units Range Error Code Bytes BOOL Spare1 BOOL Loss_Exc_Flt_Out_En Loss Excitation Fault Output 0=Disabled, Enable 1=Enabled BOOL OEL_En...
  • Page 160 Chapter 6 CGCM-DLR Unit Software Interface Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4 Byte Size in Type Bits Tag Name Description Units Range Error Code Bytes GenVT_Config Generator Voltage Transformer 1 = single-phase Configuration 2 = two- transformer open delta 3 = three-wire...
  • Page 161 CGCM-DLR Unit Software Interface Chapter 6 Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4 Byte Size in Type Bits Tag Name Description Units Range Error Code Bytes Real VperHz_HiSlope Volts per Hz Upper Slope 0…3 /PUHz Real VperHz_LoKneeFreq Volts per Hz Low Knee Frequency Hz 15…90...
  • Page 162 Chapter 6 CGCM-DLR Unit Software Interface Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4 Byte Size in Type Bits Tag Name Description Units Range Error Code Bytes Real UEL_Curve_W_Pt4 Under-excitation Limiting Curve 0…1E+09 Power Point 4 Real UEL_Curve_W_Pt5 Under-excitation Limiting Curve 0…1E+09...
  • Page 163: Introduction

    Chapter Troubleshooting Introduction This chapter lists suggested diagnostic and corrective action procedures for various common generator system malfunctions. If the suggested actions do not resolve the anomaly, contact Rockwell Automation technical support. Information on Rockwell Automation support can be found on the back cover. This chapter does not include procedures to diagnose or correct issues that are related to the basic communication between the CGCM-DLR unit and its host Logix controller.
  • Page 164 Chapter 7 Troubleshooting Table 19 - Excitation Control - FCR Symptom Most Likely Cause Diagnostic Action Corrective Action Excitation output is greater than FCR not selected/enabled Check excitation FCR select Correct Logix controller logic or I/O setpoint as required Wiring error Check wiring for excitation current Correct wiring as required output, fuses open, grounding, and...
  • Page 165 Troubleshooting Chapter 7 Table 20 - Excitation Control - AVR Symptom Most Likely Cause Diagnostic Action Corrective Action Voltage output is less than setpoint AVR not selected/enabled Check excitation enable (hardware Correct Logix controller logic or I/O and software) and AVR select as required Wiring error Check wiring for excitation enable,...
  • Page 166 Chapter 7 Troubleshooting Table 20 - Excitation Control - AVR Symptom Most Likely Cause Diagnostic Action Corrective Action Voltage output is greater than AVR not selected / enabled Check excitation AVR select Correct Logix controller logic or I/O setpoint as required Wiring error Check wiring for excitation current Correct wiring as required...
  • Page 167 Troubleshooting Chapter 7 Table 21 - Reactive Power Control - PF Symptom Most Likely Cause Diagnostic Action Corrective Action Power Factor not at PF setpoint PF not enabled Check input tag PF_Ened If not enabled, select appropriate modes of operation to enable PF mode Gain misadjusted Observe response of PF to changes...
  • Page 168 Chapter 7 Troubleshooting Table 23 - Compensation Modes - Droop Symptom Most Likely Cause Diagnostic Action Corrective Action Voltage does not change with Droop not selected/active Check tag Droop_Ened If not active, check/correct logic for changes in reactive load while not mode selection connected to the grid Cross current mode is...
  • Page 169 Troubleshooting Chapter 7 Table 24 - Compensation Modes - Cross Current Symptom Most Likely Cause Diagnostic Action Corrective Action VARs do not share at all and when a Cross current mode is not Check Droop_CCCT_Select tag If not active, check/correct logic for voltage adjust is made, reactive enabled/selected mode selection...
  • Page 170 Chapter 7 Troubleshooting Table 27 - Limiting Modes - OEL Symptom Most Likely Cause Diagnostic Action Corrective Action Excitation Current exceeds the OEL not enabled Check tag OEL_En and configuration Correct logic or configuration programmed OEL limit (OEL does not as required limit/activate) OEL Gain misadjusted...
  • Page 171 Troubleshooting Chapter 7 Table 29 - Synchronizing Symptom Most Likely Cause Diagnostic Action Corrective Action No close indication from CGCM-DLR Phase not matched Observe Phase match tag during If phase match indicated, check unit synchronization close command tag. If no phase match indicated, check phase match error Observe phase error reported by...
  • Page 172: Metering

    Chapter 7 Troubleshooting Metering If there is a difference between the metering data reported by the CGCM-DLR unit and a reference meter, verify the metering that is used to determine CGCM-DLR unit malfunction is being correctly used and in calibration. Table 30 - Metering Symptom Most Likely Cause...
  • Page 173 Troubleshooting Chapter 7 Table 30 - Metering Symptom Most Likely Cause Diagnostic Action Corrective Action KW does not read correctly CT wiring error See Current troubleshooting in this See Current troubleshooting in this table. Observe kVA indicated. If kVA table. and voltage are correct, verify CT phase rotation VT wiring error...
  • Page 174: Communication

    Chapter 7 Troubleshooting Communication The network and module status indicators indicate the state of the EtherNet/IP network that is connected into the RJ45 jacks. The following table describes the status indicator states. Table 31 - Network Status (NS) Indicator Status Indicator State Description No power or no IP address Green...
  • Page 175: Redundancy

    Troubleshooting Chapter 7 Redundancy Table 33 - Redundancy Symptom Most Likely Cause Diagnostic Action Corrective Action Both CGCM-DLR units operate as Serial cable is not properly Disable excitation to one If excitation turns off as commanded primary (both provide excitation to connected CGCM-DLR unit (one remaining unit operating),...
  • Page 176 Chapter 7 Troubleshooting Table 34 - Protection Symptom Most Likely Cause Diagnostic Action Corrective Action Generator overvoltage (59) Rapid loss of large load Gains mis-adjusted Check AVR gains Calculate/adjust gains as required Generator undervoltage (27) Over load Wiring error Check VT wiring. See Voltage Correct wiring as required metering troubleshooting Loss of sensing (60FL)
  • Page 177: General

    Appendix Time Over-current Characteristic Curves General The CGCM-DLR unit time over-current protection function provides time/current characteristic curves that closely emulate most of the common electromechanical, induction disk relays manufactured in North America. To improve further relay coordination, selection of integrated reset or instantaneous reset characteristics is also provided.
  • Page 178: Time Over-Current Characteristic Curve Graphs

    Appendix A Time Over-current Characteristic Curves Table 35 - 51P and 51N Time Characteristic Curve Constants Curve Curve Name Trip Characteristic Constants Reset Selection S, Short Inverse 0.2663 0.03393 1.000 1.2969 0.028 0.5000 S2, Short Inverse 0.0286 0.02080 1.000 0.9844 0.028 0.0940 L1, Long Inverse...
  • Page 179: Time Dial Setting Cross-Reference

    Time Over-current Characteristic Curves Appendix A Table 36 - Characteristic Curve Cross-reference Curve Curve Name Page Similar To S, Short Inverse ABB CO-2 S2, Short Inverse GE IAC-55 L, L1, Long Inverse ABB CO-5 L2, Long Inverse GE IAC-66 D, Definite Time ABB CO-6 M, Moderately Inverse ABB CO-7...
  • Page 180: Voltage Restraint

    Appendix A Time Over-current Characteristic Curves The CGCM-DLR unit has a maximum time dial setting of 9.9. The equivalent time dial setting for the electromechanical maximum setting is provided in the cross-reference table even if it exceeds 9.9. The cross-reference allows interpolation as noted.
  • Page 181 Time Over-current Characteristic Curves Appendix A Figure 43 - Time Characteristic Curve S, S1 Short Inverse, 99…1369 (similar to ABB CO-2) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 182 Appendix A Time Over-current Characteristic Curves Figure 44 - Time Characteristic Curve S2, Short Inverse, 99…1595 (similar to GE IAC-55 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 183 Time Over-current Characteristic Curves Appendix A Figure 45 - Time Characteristic Curve L, L1, Long Inverse, 9 9…1370 (similar to ABB-CO5) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 184 Appendix A Time Over-current Characteristic Curves Figure 46 - Time Characteristic Curve L2, Long Inverse, 99…1594 (similar to GE IAC-66) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 185 Time Over-current Characteristic Curves Appendix A Figure 47 - Time Characteristic Curve D, Definite Time, 99…1371 (similar to ABB-CO6) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 186 Appendix A Time Over-current Characteristic Curves Figure 48 - Time Characteristic Curve M, Moderately Inverse, 99…1372 (similar to ABB CO-7) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 187 Time Over-current Characteristic Curves Appendix A Figure 49 - Time Characteristic Curve I, I1 Inverse Time, 99…1373 (similar to ABB CO-8) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 188 Appendix A Time Over-current Characteristic Curves Figure 50 - Time Characteristic Curve I2, Inverse Time, 99…1597 (similar to GE IAC-51) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 189 Time Over-current Characteristic Curves Appendix A Figure 51 - Time Characteristic Curve V, V1, Very Inverse, 99…1374 (similar to ABB CO-9) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 190 Appendix A Time Over-current Characteristic Curves Figure 52 - Time Characteristic Curve V2, Very Inverse, 99…1596 (similar to GE IAC-53) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 191 Time Over-current Characteristic Curves Appendix A Figure 53 - Time Characteristic Curve E, E1, Extremely Inverse, 99…1375 (similar to GE IAC-11) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 192 Appendix A Time Over-current Characteristic Curves Figure 54 - Time Characteristic Curve E2, Extremely Inverse, 99…1598 (similar to GE IAC-77) Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 193 Time Over-current Characteristic Curves Appendix A Figure 55 - Time Characteristic Curve A, Standard Inverse, 99…1621 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 194 Appendix A Time Over-current Characteristic Curves Figure 56 - Time Characteristic Curve B, Very Inverse, 99…1376 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 195 Time Over-current Characteristic Curves Appendix A Figure 57 - Time Characteristic Curve C, Extremely Inverse, 99…1377 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 196 Appendix A Time Over-current Characteristic Curves Figure 58 - Time Characteristic Curve G, Long Time Inverse, 99…1622 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 197: Introduction

    Appendix CGCM-DLR Unit Math Models Introduction This appendix contains the mathematical model of the CGCM-DLR unit excitation systems. The rotating rectifier model is based on the type AC8B model available in the reference Computer Models for Representation of Digital-Based Excitation Systems in the IEEE Transactions on Energy Conversion September 1996, Vol.
  • Page 198: Voltage Regulator

    Appendix B CGCM-DLR Unit Math Models Voltage Regulator Per-unit Block Diagram for Rotating Rectifier Excitation System shows the model of the CGCM-DLR excitation system that is used with a brush-type rotating exciter. The rotating exciter parameters are not included in this discussion because they are the responsibility of the exciter manufacturer.
  • Page 199: Var/Power Factor Controller

    CGCM-DLR Unit Math Models Appendix B VAR/Power Factor The VAR/PF controller is a summing point type controller and creates the outside loop of a two-loop system. This controller is implemented as a slow PI Controller type controller. The voltage regulator forms the inner loop and is implemented as a fast PID controller.
  • Page 200 Appendix B CGCM-DLR Unit Math Models The operating characteristics are designed to mimic the characteristics of the limiter on the P-Q plane. The desired UEL curve is generated based on the user input points. Typical UEL reference is illustrated in Under-excitation Limiter Reference.
  • Page 201: V/Hz Limiter

    CGCM-DLR Unit Math Models Appendix B Figure 65 - Per-unit Block Diagram for Over-excitation Limiter Figure 66 - Over-excitation Limiter Reference Reference Field Current (I OEL_REF Count Down For Reset Time (s) V/Hz Limiter V/Hz limiter is designed to help protect the generator and step-up transformer from damage due to excessive magnetic flux that results from low frequency operation and/or overvoltage.
  • Page 202: Soft Start Control

    Appendix B CGCM-DLR Unit Math Models Soft Start Control The soft start control function is provided to cause orderly build-up of terminal voltage from the residual voltage to the rated voltage in desired time with minimal overshoot. In CGCM-DLR units, the fast dynamic response is used while the voltage reference is adjusted based on the elapsed time.
  • Page 203: Field Current Regulator

    CGCM-DLR Unit Math Models Appendix B Field Current Regulator Per-unit Block Diagram for Rotating Rectifier Excitation System shows the model of the field current regulator that is used with a brush-type rotating exciter. is the input from the power source for the excitation system. Typical value for T is 0.
  • Page 204 Appendix B CGCM-DLR Unit Math Models Notes: Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 205: Ethernet/Ip Dlr Application Objects

    Appendix Additional EtherNet/IP Network Information EtherNet/IP DLR In addition to the standard adapter class EtherNet/IP® core objects, the CGCM-DLR unit also supports these application-specific objects: Application Objects • Identity Object • Assembly Object Data Types The controller data types that are used by the CGCM-DLR unit Assembly Objects are shown in Table Table 38 - EtherNet/IP DLR Data Types Table...
  • Page 206 See Table 41 Device Status Serial Number UDINT Unique device serial number-factory assigned Product Name CHAR[] ’1407-CGCM-DLR’ Identity Object Instance 2 (Communication module device instance) Instance 2 of the Identity Object is the communication module. Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 207 Additional EtherNet/IP Network Information Appendix C The Get Attributes All service for instance 2 of the Identity Object returns the following information. Table 41 - Get Attributes All (Service Code 0x01) Name Attribute Data Type Value Vendor Id UINT 0x5A (HMS Industrial Networks) Device Type UINT 0x2B...
  • Page 208: Assembly Object (Class Code 0X04)

    Appendix C Additional EtherNet/IP Network Information Reset Service Code The CGCM-DLR unit supports type 0 and type 1 reset requests. Type 0 emulates a power cycling, while type 1 sets an ’out of box’ configuration and then performs a power cycling of the unit. Instance 1 or instance 2 of the Identity Object supports the Reset service.
  • Page 209: Specifications

    Appendix Specifications The CGCM-DLR unit electrical and physical characteristics are listed in the following tables. Control Power Supply Burden 18…32V DC (24V DC nom) 30 W (A 24V Nominal Battery or 24V DC Power Supply with ATEX certification powers the unit.) AC ripple, max 50%, 50…120 Hz Waste Electrical and Electronic Equipment (WEEE)
  • Page 210: Generator Voltage Sensing

    Appendix D Specifications Generator Voltage Sensing Phase Wiring Grounded Voltage Range for Frequency Range Configurations Connection Specified for Specified Available Accuracy Accuracy Single-phase V Gen A and Min 57 Vrms Min 20 Hz V Gen C Max 150 Vrms Max 90 Hz Three-phase Floating Wye Min 99 Vrms L-L...
  • Page 211: Bus Voltage Sensing

    Specifications Appendix D Bus Voltage Sensing Phase Wiring Grounded Voltage Frequency Configurations Connection Available Single-phase V Bus A and Min 57 Vrms Min 20 Hz V Bus C Max 150 Vrms Max 90 Hz Three-phase Floating Wye Min 99 Vrms L-L Min 20 Hz Max 208 Vrms L-L Max 90 Hz...
  • Page 212: Remote Excitation Enable Input

    Appendix D Specifications Remote Excitation Enable Input Attribute Value Voltage rating 24V DC nom 5.6K Ω Input impedance Logical high voltage, min 18V DC Logical low voltage, max 5V DC Open Collector Outputs (fault relay and redundancy relay) Attribute Value Voltage rating 24V DC nom Voltage range...
  • Page 213: Regulation

    Specifications Appendix D Regulation The following modes are used to regulate the CGCM-DLR unit. AVR Operating Mode • Accuracy: ±0.25% over the load range at rated power factor and constant generator frequency. • Steady State Stability: ±0.1% at constant load and generator frequency. •...
  • Page 214: Over-Excitation Voltage Protection

    Appendix D Specifications Over-excitation Voltage Protection Attribute Range Increment Pickup 1…200V DC 1V DC Time delay 0.1…30 s 0.1 s Over-current Protection Attribute Range Increment Accuracy Pickup 10…320% of rated ±2% rated current generator current Time delay Characteristic inverse 0.1 s per ANSI C50.13 configurable Undervoltage Protection...
  • Page 215: Loss Of Pmg

    Specifications Appendix D Loss of PMG Attribute Value Pickup < 10V AC single-phase, < 50V AC 3-phase or an imbalance greater than 20% Response time < 400 ms Reverse VAR Attribute Range Increment Accuracy Time delay 0.10…300 s 0.10 s ±0.1 s Over/Under-frequency Attribute...
  • Page 216: Phase Rotation Check

    Appendix D Specifications Rotating Diode Monitor - Open and Shorted Diode Inhibit Levels Attribute Value Field current < 1.5 A DC Generator frequency < 45 Hz Generator frequency >70 Hz Phase Rotation Check Attribute Range Accuracy Pickup 67% of rated voltage ±2% of rated voltage Time delay ±0.1 s...
  • Page 217: Over-Excitation Limiting - Offline

    Specifications Appendix D Over-excitation Limiting - Offline Attribute Range Increment Pickup 0…15 A DC 0.1 A DC Time delay 0…10 s Under-excitation Limiting Attribute Value Real power 0…100% kW for each of five points Reactive power 0…100% kVAR for each of five points Manual Excitation Control Attribute Value...
  • Page 218: Environment

    Appendix D Specifications Environment Attribute Value Temperature, operating -20…70 °C (-4…158 °F) Temperature, storage -40…85 °C (-40…185 °F) Humidity, operating 5…95% (noncondensing) Shock, operating 30 g Shock, nonoperating 50 g in 3 perpendicular planes Vibration, operating 10…500 Hz, 5.0 g / 0.015 in. Max (p-p) 2 hours each axis Dielectric strength Tested per IEEE 421.3...
  • Page 219: Physical Characteristics

    Specifications Appendix D Physical Characteristics Attribute Value Width 247.7 mm (9.75 in.) Height 355.6 mm (14.00 in.) Depth 209.6 mm (8.25 in.) Weight 7.7 kg (17 lb) Heat dissipation 3.1 kW max Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 220 Appendix D Specifications Notes: Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 221: Detailed Cgcm-Dlr Unit Tag Descriptions

    Appendix Detailed CGCM-DLR Unit Tag Descriptions Generator Parameters and This section describes the generator parameters and configuration status input and output tags for the CGCM-DLR unit. Configuration Status Inputs to CGCM-DLR Unit • GenVT_Pri_V – This tag defines the rated primary voltage for the Generator potential transformers.
  • Page 222: Outputs From Cgcm Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions • PMG_Shunt_Select - This tag selects whether the CGCM-DLR unit receives power-input voltages from the generator terminals (shunt) or from a permanent magnet generator (PMG). If PMG is selected, then the information for the PMG Phase Select parameter must be provided. •...
  • Page 223: Avr Mode

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E • HardwareExcEned – This tag reports the state of the Excitation Input [EX-D(+), EX-D(-) terminals on Terminal Block TB7]. Field excitation is disabled when this bit is in a 0 state. • SoftwareExcEned – This tag reports the state of the SoftwareExcEn tag. •...
  • Page 224: Avr Mode Outputs From Cgcm-Dlr Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions AVR Mode Outputs from CGCM-DLR Unit The AVR mode has one output. • AVR_FCR_Selection – This tag reports the selection of AVR or FCR control (see AVR_FCR_Select). FCR Mode This section describes the FCR mode inputs and outputs for the CGCM-DLR unit.
  • Page 225: Power Factor Mode

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Power Factor Mode This section describes the Power Factor mode inputs and outputs for the CGCM-DLR unit. Inputs to CGCM Unit The Power Factor mode has these inputs: • PF_VAR_Select – This tag lets you select PF or VAR control. •...
  • Page 226: Var Mode

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions VAR Mode This section describes the VAR mode inputs and outputs for the CGCM-DLR unit. Inputs to CGCM Unit The VAR mode has these inputs. • PF_VAR_Select – This tag lets you select PF or VAR control. •...
  • Page 227: Excitation Control Features

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Excitation Control Features This section describes the excitation control features. Soft Start Inputs to CGCM-DLR Unit • SoftStart_InitLevel - This tag configures the generator voltage that is generated immediately after enabling the CGCM-DLR unit. This parameter is based on a percentage of the nominal generator voltage.
  • Page 228: Over-Excitation Limit Inputs To Cgcm-Dlr Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions Over-excitation Limit Inputs to CGCM-DLR Unit • OEL_En – The setting of this tag enables the Over-excitation Limiting function. • OEL_Kg - This tag lets you adjust the proportional gain of the Over-excitation limiter. It also determines the response of the limiter to an Over-excitation event.
  • Page 229: Line-Drop Compensation Inputs To Cgcm-Dlr Unit

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Line-drop Compensation Inputs to CGCM-DLR Unit • LineDropComp - This tag configures the amount of voltage droop that is experienced during paralleling generator applications. Under-excitation Limit Inputs to CGCM-DLR Unit • UEL_En - The setting of this tag enables the Under-excitation Limiting function.
  • Page 230: Under-Excitation Limit Outputs From Cgcm Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions • UEL_Curve_VAR_Pt5 - This tag is used as the VAR coordinate in the fifth watt, VAR coordinate pair, that, in combination with four other watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting curve. Under-excitation Limit Outputs from CGCM Unit •...
  • Page 231: Loss Of Excitation Outputs From Cgcm Unit

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Loss of Excitation Outputs from CGCM Unit • LossExcFlt - This tag is used to communicate the occurrence of a Loss of Excitation Fault to the host Logix controller. When this tag is a 1, it indicates that a fault has occurred.
  • Page 232: Generator Overvoltage Outputs From Cgcm Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions Generator Overvoltage Outputs from CGCM Unit • Ovr_V_Flt – This tag is used to communicate the occurrence of an overvoltage Fault to the host Logix controller. When this tag is a 1, it indicates that a fault has occurred.
  • Page 233: Loss Of Operating Power Inputs To Cgcm-Dlr Unit

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Loss of Operating Power Inputs to CGCM-DLR Unit • LossPMGFltOutEn - When this tag is a 1 in the configuration, and a Loss of PMG Fault occurs the Fault Relay is energized. When this tag is a 0 in the configuration, a Loss of PMG Condition has no effect on the Fault Relay.
  • Page 234: Definite Time Over-Frequency Outputs From Cgcm Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions Definite Time Over-frequency Outputs from CGCM Unit • OvrFreqFlt - This tag is used to communicate the occurrence of an Over-frequency Fault to the host Logix controller. When this tag is a 1, it indicates that a fault has occurred.
  • Page 235: Reverse Power Protection Outputs From Cgcm Unit

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Reverse Power Protection Outputs from CGCM Unit • RevPwrFlt - This tag is used to communicate the occurrence of a Reverse Power Fault to the host Logix controller. When this tag is a 1, it indicates that a fault has occurred.
  • Page 236: Phase Rotation Check Outputs From Cgcm-Dlr Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions Phase Rotation Check Outputs from CGCM-DLR Unit • PhRotFlt - This tag is used to communicate the occurrence of a Phase Rotation Fault to the host Logix controller. When this tag is a 1, it indicates that a fault has occurred.
  • Page 237: Synchronizing Inputs To Cgcm Unit

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Synchronizing Inputs to CGCM Unit • AutoSyncEn – This tag is used to configure the CGCM-DLR unit to perform Auto-Synchronization. This mode is one of three synchronization modes, each selected by their respective tag. Only one can be active (1) or the SyncModeConflict tag is activated and the synchronization fails (indicated by SyncFailure tag).
  • Page 238: Synchronizing Outputs From Cgcm-Dlr Unit

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions • DeadBusGenV_LoLim - This tag configures the minimum voltage that must be present on the generator to allow the breaker to close under a Dead Bus condition. • DeadBusGenV_HiLim - This tag configures the maximum voltage that must be present on the generator to allow the breaker to close under a Dead Bus condition.
  • Page 239 Detailed CGCM-DLR Unit Tag Descriptions Appendix E • GenRot_ABC_ACB – This tag reports the rotation sequence of the generator bus in 3-phase metering. In single phase metering, these bits reflect the configuration value. • PhRotMatch – This tag reports that the phase rotation between the two busses to be synchronized matches, and is acceptable for synchronizing.
  • Page 240: Load Sharing

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions Load Sharing This section describes the load sharing inputs and outputs for the CGCM-DLR unit. Load Sharing Inputs to CGCM Unit • kVAR_LS_BridgeEn – This tag is reserved for future use. • kVAR_LS_En – This tag is reserved for future use. •...
  • Page 241 Detailed CGCM-DLR Unit Tag Descriptions Appendix E • kVAR_LS_InputV - The product of the RMS magnitude of the reactive portion of the differential current flowing in the input CT and the generator terminal voltage is computed. The product is divided by the rated kVA to determine the reported value for this tag.
  • Page 242: Metering

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions Metering This section describes the metering inputs and outputs for the CGCM-DLR unit. Metering Inputs to CGCM Unit • Set_kW_Hrs – When this tag is set to a 1, the value of the tag kWHoursPreset is loaded into the counter.
  • Page 243 Detailed CGCM-DLR Unit Tag Descriptions Appendix E • PhA_kVAR - This tag reports the kVAR being produced by Generator Phase A. • PhB_kVAR - This tag reports the kVAR being produced by Generator Phase B. • PhC_kVAR - This tag reports the kVAR being produced by Generator Phase C.
  • Page 244: Redundancy

    Appendix E Detailed CGCM-DLR Unit Tag Descriptions • ExcRipple – This tag reports the Ripple Current component of the Excitation Current. • kW_Hrs – This tag reports the cumulative kWHours produced by the Generator. • kVAR_Hrs – This tag reports the cumulative kVARHours produced by the Generator.
  • Page 245: Redundancy Outputs From Cgcm-Dlr Unit

    Detailed CGCM-DLR Unit Tag Descriptions Appendix E Redundancy Outputs from CGCM-DLR Unit • CGCM_Flt - This tag indicates, if the CGCM-DLR unit is still capable, that the CGCM-DLR unit has a detected an internal failure. • CGCMInControl - This tag indicates that the CGCM-DLR unit has hardware and software excitation enabled.
  • Page 246 Appendix E Detailed CGCM-DLR Unit Tag Descriptions Notes: Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 247: Generator Information

    Appendix Configuration Record Worksheet We suggest you use these charts to record the initial configuration settings of the CGCM-DLR unit for each generator. Make a copy of this appendix for each generator to be controlled. After entering the data and settings, keep this information for future reference.
  • Page 248: Cgcm-Dlr Unit Configuration Settings

    Appendix F Configuration Record Worksheet CGCM-DLR Unit Configuration Settings Table 45 - Generator Tab Parameter Units Setting Rated frequency Rated voltage V AC Rated current A AC Rated power Rated field voltage V DC Rated field current A DC Table 46 - Transformers Tab Parameter Units Setting...
  • Page 249 Configuration Record Worksheet Appendix F Table 47 - Excitation Tab Parameter Units Setting Soft start initial voltage Soft start time Excitation select PMG or shunt PMG phase select Single or three Loss of excitation current setpoint A DC Loss of excitation current delay Rotating diode fault open diode level % ripple Rotating diode fault delay...
  • Page 250 Appendix F Configuration Record Worksheet Table 49 - Over-excitation Limiting (OEL) Tab Parameter Units Setting Online high-level setpoint A DC Online high-level time delay Online medium-level setpoint A DC Online medium-level time delay Online low-level setpoint A DC Offline high-level setpoint A DC Offline high-level time delay Offline low-level setpoint...
  • Page 251 Configuration Record Worksheet Appendix F Table 50 - Under-excitation Limiting (UEL) Tab Parameter Units Setting UEL Curve kW point #1 UEL Curve kW point #2 UEL Curve kW point #3 UEL Curve kW point #4 UEL Curve kW point #5 UEL Curve kVAR point #1 kVAR UEL Curve kVAR point #2...
  • Page 252 Appendix F Configuration Record Worksheet Table 51 - Gain Tab Parameter Setting Power factor integral gain Ki Power factor overall gain Kg VAR integral gain Ki VAR overall gain Kg OEL integral gain Ki OEL proportional gain Kg UEL integral gain Ki UEL proportional gain Kg AVR control proportional gain Kp AVR control integral gain Ki.
  • Page 253 Configuration Record Worksheet Appendix F Table 53 - Sync Tab Parameter Units Setting Frequency match lower limit Frequency match upper limit Voltage match lower limit Voltage match upper limit Phase match lower limit Phase match upper limit Acceptance delay Bus A voltage multiplier Bus A offsets phase Bus B voltage multiplier Bus B offsets phase...
  • Page 254 Appendix F Configuration Record Worksheet Table 55 - Voltage Tab Parameter Units Setting Overvoltage Setpoint (percent of rated) Overvoltage Time Delay Undervoltage Setpoint (percent of rated) Undervoltage Time Delay Over-excitation Voltage Setpoint V DC Over-excitation Time Delay Droop Percentage Line Drop Voltage Compensation Table 56 - Current Tab Parameter Units...
  • Page 255: Introduction

    Introduction This appendix shows how to install the Add-on Profile (AOP) of the 1407-CGCM-DLR module with the Logix Designer application. Add-on Profiles are files that you add to your Rockwell Automation product library. The files contain the pertinent information for configuring a device to be connected to a Logix controller over the EtherNet/IP®...
  • Page 256 Appendix G Installing the Add-on Profile 2. Select Add-On Profiles. 3. Click Downloads 4. Click Select Files. 5. Select AOP for 1407 CGCM-DLR from the list of Add-on Profiles and then click Download Cart. Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 257 Installing the Add-on Profile Appendix G 6. Click Download Now 7. If prompted, sign in to website Member Sign In 8. Accept the terms of the license agreement 9. Select Managed Download 10. Select Run. After the download is complete, you can install the profile. Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 258: Perform The Installation

    Appendix G Installing the Add-on Profile Perform the Installation Install the Add-on Profile following the on-screen instructions. Make sure that the Logix Designer application is not running before starting the installation. 1. To locate the folder where the installation files were downloaded, use Windows Explorer.
  • Page 259 Installing the Add-on Profile Appendix G The End-user License Agreement appears. 6. Click ‘accept the terms in the license agreement’ and click Next. 7. Click Install and then click Next. 8. Click Install to continue the installation. 9. When installation is complete, click Finish. Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 260 Appendix G Installing the Add-on Profile Notes: Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 261 Index transformers 91 UEL 98 AC voltage and current sensing 22 voltage 112 generator and bus voltage 22 volts hertz 95 generator current 23 pagess AC voltage sensing 22 load share 111 preparation 75 analog inputs 42 record worksheet 247 auxiliary 43 tabs 88 bus voltage sensing 42...
  • Page 262 Index discrete outputs 32 excitation output 21 gain page 100 excitation power 19 AVR FCR control 100 real power load sharing 35 other gains 103 remote excitation enable input 32 over-excitation limiting 102 terminal block 17 power factor control 101 electronic keying 81 under-excitation limiting 102 environment 218...
  • Page 263 Index line drop compensation 50 outputs 231 over-frequency 63 inputs 229 load compensator mode 197 load share page 111 load sharing 240 phase rotation check 235 inputs 240 outputs 240 inputs 235 loss of excitation outputs 236 phase rotation fault 64 current 59 inputs 230 power factor mode 225...
  • Page 264 Index two channel chart recorder 120 reverse power 215 record system parameters 76 Reverse VAR 215 rotating diode monitor 215 redundancy 71 soft start function 216 inputs 244 under-excitation limiting 217 operation 72 under-voltage protection 214 outputs 245 voltage matching 216 relay outputs 72 spin the generator 129 tracking 73...
  • Page 265 Index rotating diode monitor 127 inputs 227 under-frequency 127 user program interface 140 test redundancy operation 122 configuration messaging 141 test synch operating interfaces 143 breaker normal position 132 breaker test position 131 time over-current characteristic curves 177 time over-current graphs 178 VAR mode 226 time dial setting cross ref 179 inputs 226...
  • Page 266 Index Notes: Rockwell Automation Publication 1407-UM002B-EN-P - February 2019...
  • Page 268 Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, ControlLogix, Logix5000, Rockwell Automation, Rockwell Software, RSLinx, RSLogix, Studio 5000, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc.

Table of Contents