Appendix E
Detailed CGCM-DLR Unit Tag Descriptions

Load Sharing

240
This section describes the load sharing inputs and outputs for the CGCM-DLR
unit.

Load Sharing Inputs to CGCM Unit

• kVAR_LS_BridgeEn – This tag is reserved for future use.
• kVAR_LS_En – This tag is reserved for future use.
• kW_LS_BridgeEn – When this tag is set to 1, the CGCM-DLR unit uses
the value of kw_AnalogTargetPUValue as the kW Load Share setpoint to
provide appropriate bias to the analog units connected to the LS lines.
• kW_LS_EN -When this tag is set to 1 the CGCM-DLR unit enables the
kilowatt load share function.
• kW_LS_OutV – This tag sets the voltage that the CGCM-DLR unit
attempts to output from the load-sharing terminals.
• kVAR_LS_OutV – This tag is reserved for future use.
• LS_FS_V - This tag sets the voltage that the load share output reaches
when the generator is producing 1 p.u. kVA. The base for this calculation is
the calculated generator kVA.
• LSRate - This tag configures the time that is required for the load share
output to change the per unit amount.
• LSLimit - This tag configures the amount of per unit change that is
allowed in the load share output per unit of time.
• KWAnalogTargetPUValue – The value of this tag is used to provide the
bias to the load share lines when the kW_LS_BridgeEN tag is set to 1.
• KWDigitalTargetPUValue – This tag is reserved for future use.
• KVARAnalogTargetPUValue – This tag is reserved for future use.
• KVARDigitalTargetPUValue – This tag is reserved for future use.

Load Sharing Outputs from CGCM-DLR Unit

• kVAR_LS_Active – This tag is reserved for future use.
• kW_LS_Active - This tag follows the kW_LS_En tag setting in the
Scheduled Write tag.
• LS_Err – This tag reports the load share error that is the per unit
percentage difference between the kW_LS_OutV and the
kW_LS_InputV.
• kW_LS_InputV – This tag reports the voltage present at the load-sharing
terminals.
• kW_PU_Load - This tag reports the total p.u. kVA produced by the active
phases of the generator. The base for this calculation is the configured
generator kVA.
• kW_AnalogPU_Load – This tag reports the value of the voltage present
at the load share terminals that are divided by the configured full scale
voltage. It is the system per unit load.