Chapter 4
CGCM-DLR Unit Configuration
Table 4 - Phase Offset Guide
Generator
Single phase (line-to-line)
Single phase (line-to-line)
Open delta
Open delta
Three-wire Wye
Three-wire Wye
Three-wire Wye
Four-wire Wye
Four-wire Wye
Four-wire Wye
Four-wire Wye
110
Table 4
IMPORTANT
configurations that are shown in
configurations are possible. It is your responsibility to determine and
verify phase offset values for wiring configurations that are not depicted
in this manual.
Bus
Dual breaker (line-to-neutral)
Four-wire Wye
Dual breaker (line-to-neutral)
Four-wire Wye
Dual breaker (line-to-line)
Dual breaker (line-to-neutral)
Four-wire Wye
Dual breaker (line-to-line)
Single (connected line-to-line)
Open delta
Three-wire Wye
Dead Bus Limits
The dead bus limits define the acceptance windows for generator frequency and
voltage that is used by the CGCM-DLR unit when closing the breaker into a
dead bus. The following Configuration tab fields specify the acceptance
windows. These fields set the related tags in the Configuration table.
• Min Frequency - Tag DeadbusGenFreqLoLimit, expressed in Hertz
• Max Frequency - Tag DeadbusGenFreqHiLimit
• Min Voltage - Tag DeadbusGenV_LoLimit, expressed in volts
• Max Voltage - Tag DeadbusGenV_HiLimit
Rotation
• Generator – Specifies the generator phase rotation. Configuration table
tag GenRotABC_ACB_Select stores this value. 0 = ABC, 1 = ACB
• Bus – Specifies the bus phase rotation. Configuration table tag
BusRotABC_ACB_Select stores this value. 0 = ABC, 1 = ACB
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
provides a guide for how to adjust phase offset for wiring
Chapter
Phase Shift Offset in CGCM-DLR Synch Tab
-30
-30
-30
-30
-60
-30
-30
-30
30
30
30
2, Installation. Other wiring