Fuse
B
A
C
G

Excitation Power

Excitation power is wired to the PMG terminals, whether connected to the
generator output (Shunt Excited) or to a PMG. Connect shunt excited inputs
with a voltage transformer (VT).
PMG inputs are on TB1 and are labeled PMG A, PMG B, and PMG C, to
illustrate their respective phase relationships. Single-phase excitation power must
be connected to terminals PMG A and PMG C. Twisted, shielded cabling is
required for the PMG inputs.
See these wiring diagrams for more information.
Figure 2 - Excitation Power Connections, 3-phase PMG
PMG
Figure 3 - Excitation Power Connections, Single-phase PMG
PMG
Figure 4 - Excitation Power Connections, Single-phase Shunt
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Installation
Chapter 2
PM G A
PMG B
PMG C
SHL D 1
SHL D 1
TB1
PMG A
PMG B
PM G C
SHLD 1
SHLD 1
TB1
PMG A
PMG B
PM G C
SHLD 1
SHLD 1
TB1