Chapter 2
Installation
Table 1 - Terminal Block Label Description
Terminal Block
Wire Gauge
Range
TB3
2.6...2.1 mm
(10...12 AWG)
TB4
1.6...1.0 mm
(14...18 AWG)
TB5
TB6
TB7
1.6...1.0 mm
(14...18 AWG)
(1) When used in a dual breaker configuration, Bus A voltage input is wired from V Bus A to V Bus N and Bus B is wired from V Bus B to V Bus N.
18
Label
Description
2
ID(+)1 A
1 A cross-current compensation CT input
ID(+)5 A
5 A cross-current compensation CT input
ID(-)
Cross-current compensation CT common input
I3(+)1 A
1 A phase C CT input
I3(+)5 A
5 A phase C CT input
I3(-)
Phase C CT common input
I2(+)1 A
1 A phase B CT input
I2(+)5 A
5 A phase B CT input
I2(-)
Phase B CT common input
I1(+)1 A
1 A phase A CT input
I1(+)5 A
1 A phase A CT input
I1(-)
Phase A CT common input
2
BAT(+)
24V DC control power input
BAT(-)
24V DC control power return
FLT
Open collector fault output
RD RLY
Open collector output for redundancy relay
CH GND
Chassis ground
V Gen A
Phase A generator voltage input
V Gen B
Phase B generator voltage input
V Gen C
Phase C generator voltage input
V Gen N
Neutral generator voltage input
V Bus A
Phase A bus voltage input
V Bus B
Phase B bus voltage input
V Bus C
Phase C bus voltage input
V Bus N
Neutral bus voltage input
2
VREF(+)
Remote setpoint adjusts input
VREF(-)
Remote setpoint adjusts input return
SHLD3
Shield 3 landing points are tied together but are not connected internally to protective earth or
other unit circuitry
SHLD3
A-COM
Analog common
EX-D(+)
Excitation enable input
EX-D(-)
Excitation enable return
LS(+)
Real power load-sharing input
LS(-)
Real power load-sharing return
SHLD4
Shield 4 landing point is not connected internally to protective earth or other unit circuitry
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019