Chapter 2
Installation
38
EtherNet/IP Network Port
Two EtherNet/IP RJ45 connectors are provided on the1407-CGCM-DLR unit.
Use the thumbwheel switches on the front of the CGCM unit to set the
EtherNet/IP network IP address
two digits of the 192.168.1.1xy static IP address. Thumbwheel switch selection
99 is used for DHCP selection or manual configuration of the IP address by
using Logix Designer application. The selection 88 is reserved for initiating an
out-of-box reset.
The thumbwheel switches are read-only when the unit powers up or is
IMPORTANT
reset. After power-up, changes to the switch settings do not affect the
network configuration of the unit.
(1) For additional information, see EtherNet/IP Media Planning and Installation Manual ODVA Pub. 148 and
EtherNet/IP Network Infrastructure Guidelines ODVA Pub. 35. ODVA membership is required.
http://odva.org/Home/ODVATECHNOLOGIES/EtherNetIP/EtherNetIPLibrary/tabid/76/lng/en-US/Default.aspx
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
(1)
. The two thumbwheel-switches set the last
SWITCH VALUES
IP ADDRESS
192.168.1.1XY
00-87,
89-98
XY = VALUES OF SWITCHES X,Y
RESTORE FACTORY
88
DEFAULTS
SELECTED PER DHCP
99
OR USER DEFINED