Regulation; Parallel Compensation; Loss Of Excitation - Allen-Bradley 1407-CGCM-DLR User Manual

Combination generator control module
Table of Contents

Advertisement

Regulation

The following modes are used to regulate the CGCM-DLR unit.
AVR Operating Mode
• Accuracy: ±0.25% over the load range at rated power factor and constant
generator frequency.
• Steady State Stability: ±0.1% at constant load and generator frequency.
• Temperature Drift: The maximum error due to temperature drift is
0.005% of full scale per degrees Celsius for voltage and current
measurements and 0.010% of full scale per degree Celsius for watt and
VAR measurements.
• V/Hz Characteristic: Slope from 0 to 3PU is adjustable in 0.1PU
increments. Two knees and two slopes are available.
• Response Time: < 1 cycle.
FCR Operating Mode
• Accuracy: ±1% of rated current.
VAR Operating Mode
• Accuracy: ±0.4% of the nominal VA rating at the rated frequency.
Power Factor Mode
• Accuracy: ±0.02% of the PF setpoint for the real power between
10...100% at the rated frequency.

Parallel Compensation

Attribute
Modes
Droop adjust range
Accuracy
Line-drop compensation range

Loss of Excitation

Attribute
Pickup
Time delay
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Value
Reactive Droop
Reactive Differential (cross-current)
0...30%
±0.3% of rated cross current input current
0...10% of rated voltage in 0.1% increments
Range
0.1...15 A
0.1...9.9 s
Specifications
Appendix D
Increment
0.1 A
0.1 s
213