• The following tags determine the points that are shown in this UEL
configuration diagram. These tags are in the configuration table and are set
by the like-named fields on the UEL page. VAR values are negative, which
indicate leading. Configure the VAR and watt tags with increasing real
power values in point 1 through point x. These tags define the curve
breakpoints. As shown, the curve continues horizontally left from point 1
and vertically up from point 5. The tags are expressed in watts or VARs
respectively.
– Point 1 is defined by tags UEL_Curve_W_Pt1 and
UEL_Curve_VAR_Pt1
– Point 2 is defined by tags UEL_Curve_W_Pt2 and
UEL_Curve_VAR_Pt2
– Point 3 is defined by tags UEL_Curve_W_Pt3 and
UEL_Curve_VAR_Pt3
– Point 4 is defined by tags UEL_Curve_W_Pt4 and
UEL_Curve_VAR_Pt4
– Point 5 is defined by tags UEL_Curve_W_Pt5 and
UEL_Curve_VAR_Pt5
• Validate and Graph button – Updates the graph in the UEL tab after
entering new values.
Related Parameters
• UEL_En tag in the Output table
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
CGCM-DLR Unit Configuration
3
2
1
Real Power, Watts
Chapter 4
5
4
99