Metering; Metering Inputs To Cgcm Unit; Metering Outputs From Cgcm-Dlr Unit - Allen-Bradley 1407-CGCM-DLR User Manual

Combination generator control module
Table of Contents

Advertisement

Appendix E
Detailed CGCM-DLR Unit Tag Descriptions

Metering

242
This section describes the metering inputs and outputs for the CGCM-DLR
unit.

Metering Inputs to CGCM Unit

• Set_kW_Hrs – When this tag is set to a 1, the value of the tag
kWHoursPreset is loaded into the counter.
• Set_kVAR_Hrs – When this tag is set to a 1, the value of the tag
kVARHoursPreset is loaded into the counter.
• Set_kVA_Hrs – When this tag is set to a 1, the value of the tag
kVAHoursPreset is loaded into the counter.
• kwHoursPreset - This value is loaded into the kW_hrs counter when
Set_kW_Hrs is asserted.
• kVARHoursPreset - This value is loaded into the kVAR_hrs counter
when Set_kW_Hrs is asserted.
• kVAHoursPreset - This value is loaded into the kVA_hrs counter when
Set_kW_Hrs is asserted.

Metering Outputs from CGCM-DLR Unit

• AvgPF- This tag reports the Average Power Factor of the active phases of
the generator.
• PhA_PF – This tag reports the Power Factor that is associated with
Generator Phase A.
• PhB_PF – This tag reports the Power Factor that is associated with
Generator Phase B.
• PhC_PF - This tag reports the Power Factor that is associated with
Generator Phase C.
• Total_kVA - This tag reports the Total kVA being produced by the active
phases of the generator.
• PhA_kVA - This tag reports the kVA being produced by Generator Phase
A.
• PhB_kVA - This tag reports the kVA being produced by Generator Phase
B.
• PhC_kVA - This tag reports the kVA being produced by Generator Phase
C.
• Total_kW - This tag reports the Total kW being produced by the active
phases of the generator.
• PhA_kW - This tag reports the kW being produced by Generator Phase A.
• PhB_kW - This tag reports the kW being produced by Generator Phase B.
• PhC_kW - This tag reports the kW being produced by Generator Phase
C.
• Total_kVAR - This tag reports the Total kVAR being produced by the
active phases of the generator.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019

Advertisement

Table of Contents
loading

Table of Contents