Appendix E
Detailed CGCM-DLR Unit Tag Descriptions
Metering
242
This section describes the metering inputs and outputs for the CGCM-DLR
unit.
Metering Inputs to CGCM Unit
• Set_kW_Hrs – When this tag is set to a 1, the value of the tag
kWHoursPreset is loaded into the counter.
• Set_kVAR_Hrs – When this tag is set to a 1, the value of the tag
kVARHoursPreset is loaded into the counter.
• Set_kVA_Hrs – When this tag is set to a 1, the value of the tag
kVAHoursPreset is loaded into the counter.
• kwHoursPreset - This value is loaded into the kW_hrs counter when
Set_kW_Hrs is asserted.
• kVARHoursPreset - This value is loaded into the kVAR_hrs counter
when Set_kW_Hrs is asserted.
• kVAHoursPreset - This value is loaded into the kVA_hrs counter when
Set_kW_Hrs is asserted.
Metering Outputs from CGCM-DLR Unit
• AvgPF- This tag reports the Average Power Factor of the active phases of
the generator.
• PhA_PF – This tag reports the Power Factor that is associated with
Generator Phase A.
• PhB_PF – This tag reports the Power Factor that is associated with
Generator Phase B.
• PhC_PF - This tag reports the Power Factor that is associated with
Generator Phase C.
• Total_kVA - This tag reports the Total kVA being produced by the active
phases of the generator.
• PhA_kVA - This tag reports the kVA being produced by Generator Phase
A.
• PhB_kVA - This tag reports the kVA being produced by Generator Phase
B.
• PhC_kVA - This tag reports the kVA being produced by Generator Phase
C.
• Total_kW - This tag reports the Total kW being produced by the active
phases of the generator.
• PhA_kW - This tag reports the kW being produced by Generator Phase A.
• PhB_kW - This tag reports the kW being produced by Generator Phase B.
• PhC_kW - This tag reports the kW being produced by Generator Phase
C.
• Total_kVAR - This tag reports the Total kVAR being produced by the
active phases of the generator.