Expanded Operating Temperature; Expanded Operating Temperature Restrictions - Dell EMC Storage NX3340 Installation And Service Manual

Table of Contents

Advertisement

Storage
Altitude
Operating
Storage
Operating temperature de-rating
Up to 35 °C (95 °F)
35 °C to 40 °C (95 °F to 104 °F)
40 °C to 45 °C (104 °F to 113 °F)

Expanded operating temperature

Expanded operating temperature
Continuous operation
≤ 1% of annual operating hours
NOTE:
When operating in the expanded temperature range, system performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD panel
and in the System Event Log.

Expanded operating temperature restrictions

Do not perform a cold startup below 5°C.
The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
150 W/8 core, 165 W/12 core and higher wattage processor [Thermal Design Power (TDP)>165 W] are not supported.
Redundant power supply unit is required.
Non-Dell EMC qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
PCIe SSD is not supported.
Tape backup unit is not supported.
20
Technical specifications
Six consecutively executed shock pulses in the positive and negative x, y, and z axes
(one pulse on each side of the system) of 71 G for up to 2 ms
3,048 m (10,000 ft)
12,000 m (39,370 ft)
Maximum temperature is reduced by 1°C/300 m (33.8°F/984.25 ft) above 950 m
(3,117 ft)
Maximum temperature is reduced by 1°C/175 m (1°F/574.14 ft) above 950 m (3,117
ft).
Maximum temperature is reduced by 1°C/125 m (1°F/410.1 ft) above 950 m (3,117 ft)
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the system can operate continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C to 40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum allowable
temperature by 1°C per 125 m above 950 m (1°F per 228 ft).