Radio Interference Emission
Interference transmission of electromagnetic fields in accordance with EN 55011: limit class
A, group 1 (measured at a distance of 10 m).
Frequency
Between 30 MHz and 230 MHz
Between 230 MHz and 1000 MHz
Emitted interference by means of network-AC power supply in accordance with EN 55011:
limit value class A, group 1.
Frequency
Between 0.15 MHz and 0.5 MHz
Between 0.5 MHz and 5 MHz
Between 5 MHz and 30 MHz
6.4

Transport and storage conditions

6.4
Requirements for Fail-Safe Modules
Fail-safe modules exceed the requirements for transport and storage in accordance with
IEC 61131, Part 2. The following details apply for fail-safe modules that are transported or
stored in the original packaging.
Type of Condition
Free fall
Temperature
Temperature change
Air pressure
Relative humidity
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
General technical specifications
6.4 Transport and storage conditions
Emitted Interference
< 40 dB (µV/m)Q
< 47 dB (µV/m)Q
Emitted Interference
< 79 dB (µV)Q, < 66 dB (µV)M
< 73 dB (µV)Q, < 60 dB (µV)M
< 73 dB (µV)Q, < 60 dB (µV)M
Permissible range
≤ 1 m
from –40 °C to +70 °C
20 K/h
1080 hPa to 660 hPa
(corresponds to an altitude of -1000 m to 3500 m)
5% to 95%, without condensation