Parameter Data Record; Parameter Assignment And Structure Of Parameter Data Record - Siemens SIMATIC ET 200SP Manual

Digital output module dq 16x24vdc/0.5a ba
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter data record

A.1

Parameter assignment and structure of parameter data record

The data record of the module has an identical structure, regardless of whether you
configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can
reconfigure the module in your user program regardless of your programming. This means
that you can use all the functions of the module even if you configured it via PROFIBUS-
GSD.
Parameter assignment in the user program
You have the option to reconfigure the module in RUN (e.g. the response of selected
channels to the CPU-STOP state can be changed in RUN without having an effect on the
other channels).
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data
record 128. The parameters set in STEP 7 are not changed in the CPU, which means that
the parameters set in STEP 7 will be valid again after a restart.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output
parameter contains a corresponding error code.
You will find a description of the "WRREC" instruction and the error codes in the STEP 7
online help.
26
DQ 16x24VDC/0.5A BA digital output module (6ES7132-6BH00-0AA0)
A
Manual, 02/2018, A5E42404662-AA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7132-6bh00-0aa0

Table of Contents