System State - ProMinent Aegis II Manual

Communication driver card
Table of Contents

Advertisement

C_meters
0x00000080
C_special
0x00000100
C_sequence
0x00000200
C_forcedon
0x00000400
C_owed
0x00000800
C_blocking
0x00002000
C_oxidant
0x00004000
C_delayed
0x00008000
C_drvfault
0x00010000
C_prebleed
0x00020000
C_ontrip
0x00100000
C_eventsp
0x00200000
C_latched
0x00800000

System State:

SYS_USB
0x00000400
SYS_LOCKED
0x00004000
SYS_NOUSD
0x08000000
control by Volume & Time
control by special control
2nd phase of an Q:P sequential volume control; ON for 'P'
prebleed has turned relay ON
time owed, count down if not blocked
Output R1 to R5, P6 to P9 is blocking another relay
one of assist, pH lockout or alt. control events is active
User set delay on flow switch
Driver card communication timeout (implies no card, card fault)
ON because prebleed active on time or uS
Set when ON setpoint exceeded, stays On until OFF setpoint exceeded
Set when Oxidant Event Setpoints override control setpoints
Contact Set controls, retains state during deadtime
USB host port active (USB thumb drive plugged in), file uploading, Pumps OFF, A/D blocked
LOCKOUT_LIMIT password fails, reset @ 7:00AM or power cycle
File System faults, no USD
// not applicable to Aegis II
// not applicable to Aegis II
Page 20 of 30