6.4.2 Wiring of Modules with HD Connectors EP-8360
When using HD-connectors EP-8360 qualified wires with a cross section between 0.14 mm² and 0.35
mm² (AWG 22 – 26) and an outer wire diameter between 1.0 und 1.6 mm (0.04 to 0.06 in) can be
connected by insulation displacement connectors (IDC). A list of SAI cables approved for the use with
HD-connectors (Document-No. GFK-2971) is available to download from the GE website.
Required tools:
•
Multi-stripax 6-16 (9202210000)
•
Pressing tool PWZ-UR20-HD
Note: When using HD-connectors EP-8360 two HD connectors must always be applied into one slot
of the connector frame.
•
Each cable must be the optimal length so the bending radii observe the manufacturer's
specifications.
•
Strip the insulation from the cable to a length of approx. 20 mm (0.8 in) using the multi-stripax
6-16.
•
Insert all wires according to wiring diagram as far as they will go into the clamping unit of the
connector. Regard the marking (pin 1 to 4) on the transparent presorter.
•
Apply the pressing tool and check whether all wires are inserted as far as they will go.
•
Press the HD connector using the pressing tool.
•
Insert the wired connector into the module's connector frame.