GE RSTi-EP User Manual page 135

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

System data
Data
Interface
System bus transfer rate
Inputs
Number
Type of load
Response time
Max. output current
Breaking energy (inductive)
Switching frequency
Actuator connection
Actuator supply
Short-circuit-proof
Protective circuit
Response time of the current limiting circuit
Module diagnosis
Individual channel diagnosis
Can be used with EP-19xx
Supply
Supply voltage
Current consumption from system current path
I
SYS
Current consumption from output current path
I
OUT
General data
Weight
For additional general data, refer to the section General Technical Data for I/O Modules
Channel
Description
0 - 3
Substitute value
GFK-2958E
Specifications EP-2614
Process, parameter and diagnostic data depend on the network
adapter used (refer to the table in section, Order and Arrangement
of the Modules)
RSTi-EP I/O communication bus
48 Mbps
4
ohmic, inductive, lamp load
low » high max. 100 μs; high » low max. 250 μs
per channel
per module
150 mJ per channel
Resistive load (min. 47 Ω)
Inductive load (DC 13)
Lamp load (12 W)
2-wire, 3-wire, 3-wire + FE
max. 2 A per plug, total max. 8 A
Yes
Constant current with thermal switch-off and automatic restart
< 100 μs
Yes
No
Yes
20.4V – 28.8V
8 mA
25 mA + load
86 g (3.03 oz)
Overview of the Editable Parameter EP-2614
Options
Off (0) / On (1)
RSTi-EP User Manual
Chapter 5 Detailed Descriptions of I/O Modules
2 A
8 A
1 kHz
0.2 Hz without free-wheeling diode
1 kHz with suitable free-wheeling
diode
1 kHz
Default
Off
131

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfk-2958e