The IP address of the virtual LAN port (the USB connection) displays under IPv4 DHCP server. The
standard IP address is 192.168.1.202. The web server is started.

9.4 Setting up Registration Data and Password Protection

If you do not set up a user, all web server functions are accessible to every user at all times. As soon
as you set up a user with password protection, users without a user ID will only have read-only rights.
Write access is blocked for them, which means that they cannot do the following:
Change parameters
Operate the station in Force mode
Load firmware updates
➢ To set up registration data and password protection
1. When you start up the web server for the first time, you are prompted to enter the
registration data. The Change login data window opens automatically. You can access this
window later via the Network Adapter status dialog box (refer to the section, 9.6):
2. Enter the User name and Password.
3. To change the login data, enter the new user name and the new password twice, click on
change login.
4. To deactivate password protection, do not enter any new data, but instead, click on No login
information.
5. If you have changed the login data, you must log back in again afterwards.