GE RSTi-EP User Manual page 117

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

System data
Data
Interface
System bus transfer rate
Inputs
Number
Sensor types
Input filter
Low input voltage
High input voltage
Sensor supply
Sensor connection
Reverse polarity protection
Module diagnosis
Individual channel diagnosis
Supply
Supply voltage
Current consumption from system current path
I
SYS
Current consumption from input current path I
General data
Weight
GFK-2958E
Chapter 5 Detailed Descriptions of I/O Modules
Specifications EP-125F
Process, parameter and diagnostic data depend on the network
adapter used (refer to the table in the section, Order and
Arrangement of the Modules)
RSTi-EP I/O communication bus
48 Mbps
16
Type 1 and Type 3 sensors as per IEC 61131-2
Input delay 3 ms
< 5 V
> 11 V
No
1-conductor
Yes
Yes
No
20.4V – 28.8V
8 mA
52 mA
IN
87 g (3.07 oz)
RSTi-EP User Manual
113

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfk-2958e

Table of Contents