Channel
Description
Temperature unit
Measurement
0 - 3
range
0 - 3
Connection type
0 - 3
Conversion time
Channel
0 - 3
diagnostics
Limit value
0 - 3
monitoring
0 - 3
High limit value
0 - 3
Low limit value
Name
Error indicator
Module type
Error byte 2
GFK-2958E
Overview of the Editable Parameter EP-3704
Options
Degree Celsius (0) / Degree Fahrenheit (1) / Kelvin (2)
PT100 -200 ... 850 Degree Celsius (0) / PT200 -200 ... 850 Degree
Celsius (1) / PT500 -200 ... 850 Degree Celsius (2) / PT1000 -200 ... 850
Degree Celsius (3) / NI100 -60 ... 250 Degree Celsius (4) / NI120 -80 ...
260 Degree Celsius (5) / NI200 -60 ... 250 Degree Celsius (6) /
NI500 -60 ... 250 Degree Celsius (7) / NI1000 -60 ... 250 Degree (8) /
Cu10 -100 ... 260 Degree Celsius (9) /
Resistance 40 Ω (10) / Resistance 80 Ω (11) / Resistance 150 Ω (12) /
Resistance 300 Ω (13) / Resistance 500 Ω (14) / Resistance 1000 Ω
(15) /
Resistance 2000 Ω (16) / Resistance 4000 Ω (17) / disabled (18)
2-wire (0) / 3-wire (1) / 4-wire (2)
240 ms (0) / 130 ms (1) / 80 ms (2) / 55 ms (3) / 43 ms (4) / 36 ms (5)
disabled (0) / enabled (1)
disabled (0) / enabled (1)
-32768 ... 32767
-32768 ... 32767
Diagnostic Data EP-3704
Bytes
Bit
0
1
2
3
0
4
5
6
7
0
1
2
3
1
4
5
6
7
2
0-7
RSTi-EP User Manual
Chapter 5 Detailed Descriptions of I/O Modules
Description
Module error
Internal error
External error
Channel error
Error
Power supply fault
Reserved
Parameter error
Module Type
Channel information available
Reserved
Reserved
Reserved
Reserved
Default
Degree Celsius
disabled
2-wire
80 ms
disabled
disabled
0
0
Default
0
0x05
1
0
0
0
0
279

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfk-2958e

Table of Contents