1.5.1 Standard Connector
The connection frame can take up to four connectors, and four conductors can be connected to
each connector. Spring-style technology allows for fine-wired conductors with crimped wire-end
ferrules or ultrasonically welded conductors, each with a maximum cross-section of 1.5 mm², to be
inserted easily through the opening in the clamping terminal without having to use tools. To insert
fine-wired conductors without wire-end ferrules, the pusher must be pressed in with a screwdriver
(refer to the section, Wiring).
Connector with Four Conductor Connectors
1.5.2 HD Connector EP-8360
The connection frame can take up to four times two HD connectors EP-8360, and qualified SAI
cables
with a cross-section from 0.14 to 0.35 mm
†
insulation displacement contact (IDC). (wiring refer to section, Wiring)
Connector EP-8360 for HD Modules
GFK-2958E
Features and Specifications:
-
conductor cross-section 0.14 to 1.5 mm²
(AWG 16 – 26)
-
maximum ampacity: 10 A
-
4-pole
The pushers are color-coded for the following
connections:
•
White Signal
•
Blue GND
•
Red 24 V DC
•
Green Functional earth (FE)
can be connected to each connector via
2
Features and Specifications:
-
conductor cross-section: 0.14 to 0.35 mm²
(AWG 22-26)
-
insulation diameter 1.0 to 1.6 mm (0.04 to
0.06")
-
maximum current capacity: 1 A
-
4-pole
RSTi-EP User Manual
Chapter 1: Introduction
14