System data
Data
Interface
System bus transfer rate
Inputs
Number
Sensor types
Input filter
Low input voltage
High input voltage
Max. input current per channel
Sensor supply
Sensor connection
Reverse polarity protection
Module diagnosis
Individual channel diagnosis
Time stamp data width
Time stamp resolution
Supply
Supply voltage
Current consumption from system current path
I
SYS
Current consumption from input current path I
General data
Weight
For additional general data, refer to the section, General Technical Data for I/O Modules
Channel
Description
0 - 3
Input delay
0 - 3
TimeStamp at edge 0-1
0 – 3
TimeStamp at edge 1-0
GFK-2958E
Specifications EP-12F4
Process, parameter and diagnostic data depend on the network
adapter used (refer to the table in the section, Order and
Arrangement of the Modules)
RSTi-EP I/O communication bus
48 Mbps
4
Type 1 and Type 3 sensors as per IEC 61131-2
Input delay adjustable from 0 to 40 ms (PROFIBUS-DP to 20 ms)
< 5 V
> 11 V
3 mA
Yes
2-wire, 3-wire, 3-wire + FE
Yes
Yes
No
16 bits
1 μs
20.4V – 28.8V
8 mA
18 mA + sensor supply current
IN
87 g (3.07 oz)
Overview of the Editable Parameter EP-12F4
Options
no (0) / 0,3 ms (1) (not at PROFIBUS-DP) / 3 ms (2) / 10
ms (3) / 20 ms (4) / 40 ms (5) (not at PROFIBUS-DP)
disabled (0) / enabled (1)
disabled (0) / enabled (1)
RSTi-EP User Manual
Chapter 5 Detailed Descriptions of I/O Modules
Default
3 ms
disabled
disabled
118