2.3 Use in a Potentially Explosive Atmosphere

If RSTi-EP products are used in potentially explosive atmospheres, the following notes are also
applicable:
Staff involved in assembly, installation and operation must be qualified to perform safe
work on electrical systems protected against potentially explosive atmospheres.
The remote I/O-System RSTi-EP shall only be used in an area of not more than pollution
degree 2, as defined in IEC 60664-1.
For applications in potentially explosive atmospheres, the requirements according to IEC
60079-15 must be observed, in particular the housing enclosing the system must meet
the requirements of explosion protection type Ex n or Ex e and protection class IP54. The
IP54 enclosure must be accessible only by the use of a tool.
Sensors and actuators that are located in Zone 2 or in a safe zone can be connected to
the RSTi-EP station.
The ambient temperature range -20°C to +60°C shall not be exceeded.
When the temperature under rated conditions exceeds 70 °C at the conductor or conduit
entry point, or 80 °C at the contact, the temperature specification of the selected cable
shall be in compliance with the actual measured temperature values.
A stabilized 24V DC power supply with double or reinforced insulation shall be used.
When using modules EP-2714, EP-2814, and EP-1804 in explosive atmosphere:
o Device shall be installed in an environment free of condensation, corrosives and
conducting dusts.
o If the switching or input voltage exceeds 63V, a transient protection device shall be
provided that limits the transients to a peak voltage of 500V or less.
For EP-2714 (Relay Module) only:
o Since relays are subject to wear, it must be ensured, by appropriate maintenance
intervals, that the temperatures do not exceed the limits of temperature class T4.
Note: A contact resistance of more than 110 milli-ohm will be considered as a fault.
o Resistive Loads Only
For EP-2714 and EP-2814 Relay Modules:
o Transient protection shall be provided that is set at a level not exceeding 140% of the
peak rated voltage value at the supply terminals to the equipment.
A visual inspection of the RSTi-EP station is to be performed once per year.
If mounted in other directions than horizontal (reference mounting rail), restrictions to the
max. operating temperature, max. output currents may apply.
While explosive atmosphere is present:
o No electrical connection shall be separated in energized condition.
o The USB interface shall not be used.
o Dip-switches, binary-switches and potentiometers shall not be actuated.
Only power supplies with secure isolation shall be used.
Refer manufacturers manual.
GFK-2958E
RSTi-EP User Manual
Chapter2: Safety
22