GE RSTi-EP User Manual page 87

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

0x1133
rw
0x1134
rw
0x1135
rw
0x1136
rw
0x1137
rw
0x113C – 0x113D
wo
0x113E – 0x113F
wo
0x1140 – 0x1141
rw
0x1142 – 0x1143
rw
0x1144 – 0x1145
rw
0x27FE
ro
0x27FF
ro
0x2800 – 0x287F
rw
0x2A00 – 0x2A7F
ro
0x8000 – 0x87FF
ro
0x9000 – 0x97FF
rw
0xA000 – 0xA7FF
ro
0xB000 – 0xB7FF
ro
0xC000 - 0xC7FF
rw
(Firmware 01.xx.xx)
0xC000 - 0xFFFF
(Firmware 02.00.00
or higher)
Note: If the user wants to access the DWORD for EP-5111, EP-5112, EP-5212, EP-5442 and EP-5422 modules use
SWAP_DWORD function block.
Function
Function
code no.
1
Read Coils
2
Read Discrete Inputs
3
Read Holding Registers
4
Read Input Registers
5
Write Single Coil
6
Write Single Registers
15
Write Multiple Coils
GFK-2958E
Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
0x0000 = disable, 0x0001 = enable
Word
Process alarm 0x0000 = disable, 0x0001 = enable
Word
Diagnostics alarm 0x0000 = disable, 0x0001 =
enable
Word
Behavior in case of field bus error and reference
list error
0x0000 = all outputs to 0, 0x0001 = set error
values
0x0002 = retain process data
Word
Behavior when module removed
0x0000 = process data continues to run
0x0001 = behavior as with field bus error
Word
Data format 0x0000 = Motorola, 0x0001 = Intel
Long
Restore module parameters
Motorola ="LOAD", Intel ="DAOL"
Long
Save module parameters
Motorola ="SAVE", Intel ="EVAS"
Long
Changing IP Address 2 via Fieldbus
Long
Changing Subnet Mask 2 via Fieldbus
Long
Changing Gateway 2 via Fieldbus
Word
Number of entries in the current module list
Word
Number of entries in the reference module list
Long
Reference module list (max. 64 modules per
station * 2 registers per module)
Long
Current module list (max. 64 modules per station *
2 registers per module)
Module
Process data inputs (max. 64 modules per station
* 32 registers per module)
Module
Process data outputs (max. 64 modules per
station * 32 registers per module)
Byte
Diagnostics (max. 64 modules per station * 32
registers per module)
Byte
Process alarms (max. 64 modules per station * 32
registers per module)
Byte
Module parameters (Firmware 01.xx.xx:
max. 64 modules per station * 32 registers per
module;
Firmware 02.00.00 or higher:
max. 64 modules per station * 256 registers per
module)
Implemented Modbus Functions
Description
Reading of output bits in the range of 0x0800 – 0x0FFF
Reading of input bits in the range of 0x0000 – 0x07FF
Reading of multiple holding registers
Reading of multiple input registers
Writing of an individual output bit in the range of 0x0800 –
0x0FFF
Writing of individual holding registers
Writing of output bits in the range of 0x0800 – 0x0FFF
RSTi-EP User Manual
Corresponds to the
"DEFAULT" in the web
server
Corresponds to
"SAVE" in the web
server
These registers only
available with
EPXMBE101
There must always be
2, 4, 6 etc. registers
transferred
There must always be
2, 4, 6 etc. registers
transferred
Confirmation by
readout
Confirmation by
readout
83