Parameter "Save module parameters" in the web server
2
The choice Yes or Standard cannot be displayed in the web server, caused by the data structure of
this parameter. The display will be reset to No anytime.
Option Yes: The current image of all module parameters is saved in the network adapter and will be
sent to the modules again during the Network adapter's next restart. Subsequent changes of the
module parameters are considered and saved only if the option Yes will be chosen again.
Option Standard: The default parameters will be loaded to the modules immediately. Subsequent
changes of the module parameters are possible, but they will get loss during the network adapter's
next restart.
Parameter "Restore module parameters"
This parameter is not editable. It will be automatically set to Yes as soon as the network adapter will
have sent saved parameter data to the modules.
(ro: read only = input register, rw: read write = holding register, wo: Write only = holding register)
Register address
Access
(in hex)
0x0000 – 0x01FF
ro
0x0800 – 0x09FF
rw
0x1000 – x1006
ro
0x100C
ro
0x1010
ro
0x1011
ro
0x1017
ro
0x1018 – 0x101B
ro
0x101C – 0x101F
ro
0x1028 – 0x102F
ro
0x1030
ro
0x1120
rw
0x1121
rw
0x1122
rw
0x1124 – 0x1125
rw
0x1126 – 0x1127
rw
0x1128 – 0x1129
rw
0x1130
rw
0x1131
rw
0x1132
rw
GFK-2958E
Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
Register Structure
Data width
Description
Module-
Packed process data for inputs
dependent
Module-
Packed process data for outputs
dependent
Byte
Network adapter identifier
Word
Network adapter status
Word
Process image length in bits for the output
modules
Word
Process image length in bits for the input modules
Word
Register mapping revision
Byte
Collective diagnostics message for I/O modules
(1 bit per I/O module)
Byte
Collective process alarm message for I/O modules
(1 bit per I/O module)
Byte
Module status (2 bits per I/O module) 00 = module
OK, 01 = module error 10 = incorrect module 11 =
module not plugged in
Word
MODBUS DATA EXCHANGE watchdog, current
time (x*10 ms) 0 = watchdog has expired 0xFFFF =
watchdog deactivated
Word
MODBUS DATA EXCHANGE watchdog, predefined
time (x*10 ms), default = 0 ms (no watchdog
active)
Word
MODBUS DATA EXCHANGE watchdog reset
register
Bit0 = 1: watchdog reset at predefined time
Bit8 = 1: restart after expired watchdog
DWord
Lock of the "Force Mode" via Webserver
Long
Changing IP Address 1 via Fieldbus
Long
Changing Subnet Mask 1 via Fieldbus
Long
Changing Gateway 1 via Fieldbus
Word
MODBUS CONNECTION mode register
Word
MODBUS CONNECTION timeout in sec.
Default = 1 (0 not allowed)
Word
Check the reference list before data exchange
RSTi-EP User Manual
Remarks
byte granularly
byte granularly
Bit assignment as
with EPXETC001
Structure as in
PROFIBUS module
status
Time still remaining
for monitoring the
exchange of process
data
Time for monitoring
the exchange of
process data
Bit 0: reset watchdog
while it is running
(retrigger)
Bit 8: restart of
expired watchdog
LOCK to lock,
FREE to unlock
82