Byte
IB0
IB1
IB2
IB3
IB4
IB5
IB6
IB7
Internal process data mapping with data format "Standard". Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer
Measurement
Current (I) /
range
Voltage (U)
23.52 mA
20 mA
0 – 20 mA
10 mA
0 mA
22.81 mA
20 mA
4 – 20 mA
12 mA
4 mA
1.19 mA
11.76 V
10 V
0 – 10 V
5 V
0 V
11.76 V
10 V
5 V
±10 V
0 V
-5 V
-10 V
-11.76 V
11.41 V
10 V
2 - 10 V
6 V
2 V
0.59 V
5.7 V
5 V
1 - 5 V
3 V
1 V
0.30 V
GFK-2958E
Process Data
Format
Description
Word
Word
Word
Word
Measurement Range EP-3264
Decimal (D)
Hexadecimal
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
-4864
0xED00
32511
0x7EFFh
27648
0x6C00
13824
0x3600
0
0x0000
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
-13824
0xCA00
-27648
0x9400
-32511
0x8100
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
-4864
0xED00
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
-4864
0xED00
RSTi-EP User Manual
Chapter 5 Detailed Descriptions of I/O Modules
Inputs EP-3264
AI0
AI1
AI2
AI3
Range
Overloading
Nominal range
Overloading
Nominal range
Underloading
Overloading
Nominal range
Overloading
Nominal range
Underloading
Overloading
Nominal range
Underloading
Overloading
Nominal range
Underloading
Remarks
Conversion
D = 27648 x I / 20
I = D x 20 / 27648
D = 27648 x (I – 4) / 16
I= D x 16 / 27648 + 4
D = 27648 x U/10
I = D x 10 / 27648
D = 27648 x U / 10
U = D x 10 / 27648
D = 27648 x (U – 2) / 8
U = D x 8 / 27648 + 2
D = 27648 x (U – 1) / 4
U = D x 4 / 27648 + 1
244