System data
Data
Interface
System bus transfer rate
Galvanic isolation
Inputs
Number of counter inputs
Input filter
Low input voltage
High input voltage
Max. input current per channel
Sensor supply
Sensor connection
Reverse polarity protection
Module diagnosis
Individual channel diagnosis
Counter width
Maximum input frequency
Mode of operation
Supply
Supply voltage
Current consumption from system current path I
typ.
Current consumption from input current path I
General data
Weight
For additional general data, refer to the section, General Technical Data for I/O Modules.
GFK-2958E
Chapter 5 Detailed Descriptions of I/O Modules
Specifications EP-5212
Process, parameter and diagnostic data depend on the network
Adapter used (refer to the table in the section, Order and
Arrangement of the Modules)
RSTi-EP I/O communication bus
48 Mbps
500 V DC between the current paths
2
adjustable between 3 Hz and 187 kHz (333 ms and 5 μs)
< 5 V
> 11 V
3.5 mA
Yes
2- and 3-wire
Yes
Yes
No
32 bits
100 kHz
Pulse and direction / AB mode with 1-, 2-, 4-times sampling
20.4V – 28.8V
,
8 mA
SYS
35 mA + sensor supply current
IN
87 g (3.07 oz)
RSTi-EP User Manual