Name
Channel 0 error
to
Channel 7 error
Channel 8 error
to
Channel 31 error
Time stamp
Measurement
Current (I) /
range
Voltage (U)
23.52 mA
20 mA
0 – 20 mA
10 mA
0 mA
22.81 mA
20 mA
4 – 20 mA
12 mA
4 mA
1.19 mA
The following applies for all ranges:
input value > overload range = 0x7FFF
input value < underload range = 0x8000
GFK-2958E
Diagnostic Data EP-3468
Bytes
Bit
Description
0
Parameter Error
1
Overload
2
Reserved
3
Fuse blown
0
4
Line break
5
Reserved
6
Lower limit exceeded
7
Upper limit exceeded
19 - 42
0 - 7
Reserved
43-46
Time stamp [μs] (32 bit)
Measurement Range EP-3468
Decimal (D)
Hexadecimal
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
-4864
0xED00
RSTi-EP User Manual
Chapter 5 Detailed Descriptions of I/O Modules
Range
Conversion
Overloading
D = 27648 x I / 20
Nominal range
I = D x 20 / 27648
Overloading
D = 27648 x (I – 4) / 16
Nominal range
I= D x 16 / 27648 + 4
Underloading
Default
0
0
0
0
0
0
0
0
0
262