GE RSTi-EP User Manual page 404

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

Indicator
Active
Input supply voltage
Output supply
voltage
Indicator
Power LED
System Fault
Bus Fault
Maintenance
Required
Connection/Active
GFK-2958E
LED
Status
ACT 2
Yellow flashing: Data being
exchanged on port 2
3.1
Green: Supply voltage for input
current path > 18 V DC
3.2
Red: Supply voltage for input
current path < 18 V DC
3.4
Red: Internal fuse defective
4.1
Green: Supply voltage for output
current path > 18 V DC
4.2
Red: Supply voltage for output
current path < 18 V DC
4.4
Red: Internal fuse defective
LED
Status
PWR
Green: Supply voltage
Off, and the status LED of the
module is green: Defective
network adapter
Off, and the module status LED is
off: Improper supply voltage
Red: Configuration error, or error in
SF
the network adapter, or error in a
module, or there is a new
diagnostic message
Red flashing: Station in Force
mode
BF
Red: No connection to the fieldbus
Red flashing: Configuration error,
no connection to the control unit,
or error in the parameter set
MT
Yellow: Error on the system bus
L/A IN
Off: No connection
Green: Connection established
between port 1 of the network
adapter and another field device
Green flashing: Data being
exchanged on port 1
RSTi-EP User Manual
Chapter 12 LED Indicators and Troubleshooting
Recommended action
Check the supply voltage
Replace the network adapter
Check the supply voltage
Replace the network adapter
EPXETC001
Recommended action
Have the network adapter repaired or
replaced
The internal fuse was triggered due to an
overload
Check the supply voltage
Check that the ESI configuration file is up-to-
date
Check if the configured station setup matches
the actual setup
Read the diagnostic message with the web
server or an engineering tool and determine
which further actions to take
Check the fieldbus cable and the PLC
configuration
Check the fieldbus parameters and the PLC
configuration
Check that the ESI file is up-to-date
Check if the configured station setup matches
the actual setup
Check that the modules have been snapped
into place properly
Check the fieldbus cable
400