GE RSTi-EP User Manual page 177

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

Periodic Counting/ Primary Counting Direction Up
Up-counting starts at the load value.
If the parameterized end value -1 is reached during counting in the positive direction, the
counter jumps back to the load value at the next positive count pulse and continues counting
from there. The status bit End value reached is set and a process alarm will be triggered if it is
parameterized.
Upon reaching the lower count limit the counter jumps to the upper count limit to continue
counting from there. The status bit Underflow performed is set and a process alarm will be
triggered if it is parameterized. All status bits remain set until they are reset with the bit Reset
status bits in the control word.
Limits
End value
Lower count limit
GFK-2958E
Periodic Counting, Primary Counting Direction Up
Counting Range
Valid range of values
–2 147 483 647 (–2
+2 147 483 648 (2
RSTi-EP User Manual
Chapter 5 Detailed Descriptions of I/O Modules
31
+ 1) to +2 147 483 647 (2
)
31
31
– 1)
173