4.4.4 Configuration of the IP Address

The web server can be used to define whether a static IP address shall be used or the address shall
be assigned automatically (DHCP/BootP).
Network adapters using firmware version 01.xx.xx are preset to the static IP address 192.168.0.222.
Network adapters using firmware version 02.00.00 or higher will by default send a DHCP discover
first. If no assignment by a DHCP server follows during the next 30 seconds, the static IP address
192.168.0.222 will be set.
Overview of the Editable Parameters EPXMBE001/EPXMBE101
Parameter
IP-Address
#
Subnet mask
#
Gateway
#
IP Configuration
#
MODBUS DHCP Timeout
Additional TCP port
1
Modbus Dual LAN Mode
(EPXMBE101 ony)
IP-Address USB Port
Webserver via Ethernet
Save module parameters
2
Status Modbus watchdog
Modbus Connection
Timeout
Write access in multi-
client operation
Check reference list
before exchanging data
Process alarm
Diagnostic alarm
Behavior of outputs on
fieldbus error
Module behavior on hot
swap
Data format
Lock force mode
Change requires restart of the network adapter.
#
In Dual LAN Mode (EPXMBE101 only) parameterizable for each Ethernet Port on the Module
Parameter "Additional TCP port"
1
Another TCP port additionally to the standard port (502) can be enabled using this parameter. Apart
from the values 80 (reserved for http) and 161 (reserved for SNMP) every number from 1 to 65535 can
be used. Value 0 deactivates the port. The standard port 502 will remain open in any case.
GFK-2958E
Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
Optional values
4 numbers between 0-255
4 numbers between 0-255
4 numbers between 0-255
Static, DHCP, BootP
Waiting time, 1 to 1000 s
0 (disabled) / Value from 1 to 65535
(except for 80 and 161)
disabled / enabled
192.168.1.202; 192.168.2.202,
192.168.3.202, 192.168.4.202,
192.168.5.202
disabled / enabled
no / yes / Standard
Watchdog time in steps of 10 ms
Connection watchdog time in sec
write for all, 1stWr1stServe,
1stConn1stServe
disabled / enabled
disabled / enabled
disabled / enabled
All outputs off / Enable substitute values /
Hold last value
Continue data exchange / Behavior like
fieldbus error
Motorola / Intel
Force mode unlocked / Force mode locked
RSTi-EP User Manual
Default
192.168.0.222
255.255.255.0
192.168.0.1
DHCP and static
30 s
0
disabled
192.168.1.202
disabled
no, refer to register 0x113C – 0x113F Save
Module Parameters
0 *10 ms, refer to register 0x1120 MODBUS
DATA EXCHANGE watchdog, predefined time
1 s, refer to register 0x1131 MODBUS
CONNECTION Timeout in Sec
write for all, refer to register 0x1031
MODBUS CONNECTION Mode Register
disabled, refer to register 0x1132 Check
Reference List prior to Data Exchange
refer to register 0x1133 Process Alarm
refer to register 0x1134 Diagnostic Alarm
All outputs off, refer to register 0x1135 Field
Bus or Reference List Error Behavior
Continue data exchange, refer to register
0x1136 Module Removal Behavior
Motorola, refer to register 0x1137 Data
Format
Force mode unlocked, refer to register
General Contact Information
81