General Technical Data For I/O Modules - GE RSTi-EP User Manual

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

1.6 General Technical Data for I/O Modules

Type of connection
Dimensions
Protection class
(DIN EN 60529)
Flammability rating UL 94
Temperature data
Humidity
Air pressure
Vibration resistance
Shock resistance
Potential isolation
Approvals and Standards
Type of connection
Unless otherwise noted within the product-specific technical data.
All product-specific technical data is available in the corresponding product description in Chapter 5, Detailed Descriptions
of I/O Modules.
GFK-2958E
Spring-style
IDC (EP-3368, EP-3468)
Height
Width
Depth
IP 20
V-0
Operation
Storage, transport
Operation, storage, transport
Operation
Storage, transport
5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6
8.4 Hz ≤ f ≤ 150 Hz: 1-g acceleration as per IEC 60068-2-6
15 g over 11 ms, half sinewave, as per IEC 60068-2-27
Test voltage
Pollution severity level
Overvoltage category
cULus Ordinary Locations
UL
Hazardous Locations
C
US
Class 1 Division 2, Gr. A, B, C, D
Potentially explosive atmosphere
Zone 2
Explosion protection
EMC
FCC Compliance
PLC
Spring-style
RSTi-EP User Manual
Chapter 1: Introduction
Single-wired, fine-wired
Conductor cross-section
0.14 – 1.5 mm
2
(AWG 16 – 26)
Single-wired, fine-wired
Conductor cross-section
0.14 – 0.35 mm2 (AWG 22 – 26)
4.72 in (120.0 mm)
w/ release lever: 128.0 mm (5.04 in)
11.5 mm (0.45in)
76.0 mm (2.99 in)
-20°C to +60°C (- 4 to +140 °F)
-40°C to +85°C (- 40 to +185 °F)
5 % to 95 %, non-condensing
as per IEC 61131-2
≥ 795 hPa (altitude ≤ 2000 m)
as per IEC 61131-2
≥ 700 hPa (altitude ≤ 3000 m)
as per IEC 61131-2
max. 28.8 V within one channel
500 V DC field/system
2
II
UL 508, CSA C22.2 No. 0-M91
ISA 12.12.01: 2007
CSA C22.2 No. 213-M1987 (Reaffirmed 2008)
ATEX Directive 2014/34/EU
EN 60079-0:2012+A11:2013 and EN 60079-
15:2010
IEC 60079-0:2011 and
IEC 60079-15:2010
EN61000-6-2: 2005, EN61000-6-4: 2007 +
A1:2011, (partial standards as per the
requirements of EN61131‑2: 2007)
47 CFR 15: 2011 (Class A)
IEC 61131-2
Single-wired, fine wired
16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfk-2958e