Measurement
Current (I) /
range
Voltage (U)
5.88 V
5 V
0 – 5 V
2.5 V
0 V
5.88 V
5 V
2.5 V
±5 V
0 V
-2.5 V
-5 V
-5.88 V
The following applies for all ranges:
input value > overload range = 0x7FFF
input value < underload range = 0x8000
GFK-2958E
Measurement Range EP-3124
Decimal (D)
Hexadecimal
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
32511
0x7EFF
27648
0x6C00
13824
0x3600
0
0x0000
-13824
0xCA00
-27648
0x9400
-32511
0x8100
RSTi-EP User Manual
Chapter 5 Detailed Descriptions of I/O Modules
Range
Conversion
Overloading
D = 27648 x U/5
Nominal range
I = D x 5 / 27648
Overloading
D = 27648 x (U – 1) / 4
Nominal range
U = D x 4 / 27648 + 1
Underloading