(6) Operation example of the check code detection
When values are set for a channel with output range of -10 to 10V as follows:
Ex.
• "CH
Scaling enable/disable setting": "0: Enable"
• "CH
Scaling upper limit value": 24000
• "CH
Scaling lower limit value": -24000
• "CH
Shifting set value (RWw6 to RWw9)": -200
The error of the check code is output
when the value in CH1 Digital value
(RWw2) is greater than 24575.
Setting range
Controlled by the D/A
converter module
Controlled by the program
CH1 Set value check code (RWr2)
Latest warning code (RWr1)
Warning flag (RX7)
Error clear request flag (RYA)
ALM LED
Remote READY (RXB)
The value to be set to CH1 Digital value (RWw2)
Digital value
24575
16383
-16384
-24576
0000
H
0000
H
ON
OFF
ON
OFF
OFF
The check code is not reset
when the value is out of the
setting range.
OFF
ON
The value after the addition of
a shifting set value and the
scaling conversion
000F
00FF
H
0601
H
The check code is reset
when the value is within the
setting range.
Flashing
CHAPTER 8 FUNCTION
Time
0000
H
H
0000
H
OFF
ON
OFF
OFF
91