(4) Example of scaling setting
1: When values are set for a channel with output range of 0 to 5V as follows:
Ex.
• "CH
Scaling enable/disable setting": "0: Enable"
• "CH
Scaling upper limit value": 10000
• "CH
Scaling lower limit value": 2000
The digital values and scale-converted digital values are as follows:
Analog output voltage (V)
5V
0V
Digital value
2000
3600
5200
6800
8400
10000
0
12000 12287
Scaling lower limit
Scaling upper limit
value: 2000
value: 10000
Digital value after scale
conversion
Scale converted digital value
Digital value
Analog output voltage (V)
0
2400
4800
7200
9600
12000
CHAPTER 8 FUNCTION
0
1
2
3
4
5
81