Error code
Classification
(hexadecimal)
*1
062
Moderate error
H
*1
Moderate error
090
H
*1
Moderate error
091
H
0930
Moderate error
H
0940
Minor error
H
0950
Moderate error
H
0960
Major error
H
0970
Major error
H
Error name
Description and cause
The alert output lower limit value
has been set equal to or greater
than the alert output upper limit
value in CH1 Alert output upper
Alert output
limit value (address: 0106
upper/lower
limit value
CH4 Alert output lower limit value
inverted
(address: 010D
represents the channel
number where an error has
occurred.
The values set in CH1 Scaling
lower limit value (address:
010F
) to CH4 Scaling upper
H
Scaling setting
limit value (address: 0116
outside the
outside the range of -32000 to
range
32000.
represents the channel
number where an error has
occurred.
The scaling lower limit value has
been set equal to or greater than
the scaling upper limit value in
CH1 Scaling lower limit value
Scaling
(address: 010F
upper/lower
limit value
upper limit value (address:
inverted
0116
).
H
represents the channel
number where an error has
occurred.
Cyclic data
The value set in Cyclic data
update watch
update watch time (address:
time setting
0007
) is outside the range of 0
H
outside the
to 20.
range
Station number
The station number switch setting
switch changed
has been changed while the
error
module power is on.
Clock data
The clock data acquired from the
outside the
CPU module is invalid.
range
Network No.
changed
The network number has been
through the
changed through the network.
network
Station No.
changed
The station number has been
through the
changed through the network.
network
CHAPTER 11 TROUBLESHOOTING
Correct the settings of CH1 Alert output upper
limit value (address: 0106
) to
H
output lower limit value (address: 010D
that the alert output lower limit value is
).
H
smaller than the alert output upper limit value.
Set a value within the range of -32000 to
) are
H
32000 in CH1 Scaling lower limit value
(address: 010F
value (address: 0116
Correct the settings of CH1 Scaling lower limit
value (address: 010F
) to CH4 Scaling
H
limit value (address: 0116
scaling lower limit value is smaller than the
scaling upper limit value.
Set a value within the range of 0 to 20 in
Cyclic data update watch time (address:
0007
).
H
While the module power is on, set the switch
again to the station number that has been set
before.
There may be an influence from noise or a
hardware error. If the same error occurs again
even after measures have been taken against
noise, please consult your local Mitsubishi
representative.
Take measures against noise and reset the
module. If the same error occurs again, the
hardware of the module may be in failure.
Please consult your local Mitsubishi
representative.
Take measures against noise and reset the
module. If the same error occurs again, the
hardware of the module may be in failure.
Please consult your local Mitsubishi
representative.
Action
) to CH4 Alert
H
) so
H
) to CH4 Scaling upper limit
H
).
H
) to CH4 Scaling upper
H
) so that the
H
121
11